Micro-Ohmmeter AUTO-OHM 200 S4, DC, 200 A, for Circuit Breaker Contacts
A fifth generation microprocessor based DC micro-ohmmeter for measuring the contact resistance of extra high voltage circuit breakers, bushing joints and welded joints. It supplies current from 1 to 200 A in 1 A steps across a range of 1 µΩ to 5 Ω.
- Type
- portable micro-ohmmeter, DC
- Test current
- 1 to 200 A, in 1 A steps
- Resistance range
- 1 µΩ to 5 Ω (up to 10 mΩ at 200 A, 5 Ω at 1 A)
- Resolution
- 0.1 µΩ (1.0 to 999.9 µΩ) ... 0.01 Ω (1 to 5 Ω)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
AUTO-OHM 200 S4 is used to measure the contact resistance of extra high voltage circuit breakers, bushing contact joints, welded joints and other low resistance tasks. The unit weighs 8.9 kg.
The unit delivers true DC current from 1 to 200 A, set in 1 A steps, from a thermally protected power supply. The measuring range runs from 1 µΩ to 5 Ω: up to 10 mΩ at 200 A and up to 5 Ω at 1 A. Above 5 A the resolution reaches 0.1 µΩ. Typical accuracy is ±(0.15% of reading + 0.15% FS) across the test current range.
The rise and fall time of the current is adjustable from 5 to 10 seconds. In Auto Test mode, measurement starts as soon as the potential leads touch the two points of the current circuit, which saves time when several sections of a breaker contact system are measured in turn. The result is compared with preset limits and shown as Pass or Fail.
Data is entered on a 44-key QWERTY membrane keypad, and results are shown on a 128 x 64 dot backlit LCD. Internal memory keeps 128 records of up to 64 readings each, and up to 999 records can be saved on a USB flash drive. Analysis software for PC is included. The S4 DG adds the dual ground option, the S4 PR adds a built-in 2.5-inch thermal printer, and the S4 PRDG has both.
Operating power is 100 to 240 V AC at 50/60 Hz. Dimensions are 45.7 x 17.8 x 38.1 cm. Operating temperature is -10 to +50 °C, humidity up to 90% at 40 °C non-condensing, and altitude up to 2000 m. Electromagnetic compatibility and environmental tests are covered by the standards listed in the specification table. The kit includes #1 AWG test cables of 9.1 m, a power cord and a ground cable.
Technical specifications
| Type | portable micro-ohmmeter, DC |
|---|---|
| Test current | 1 to 200 A, in 1 A steps |
| Resistance range | 1 µΩ to 5 Ω (up to 10 mΩ at 200 A, 5 Ω at 1 A) |
| Resolution | 0.1 µΩ (1.0 to 999.9 µΩ) ... 0.01 Ω (1 to 5 Ω) |
| Typical accuracy | ±(0.15% of reading + 0.15% FS) |
| Current rise and fall | 5 to 10 s |
| Compliance | IEEE C37.09-1999, section 5.15 |
| Display | backlit LCD, 128 x 64 dots |
| Keypad | 44-key QWERTY membrane |
| Printer | 2.5-inch thermal printer (optional) |
| Internal memory | 128 records of up to 64 readings |
| External memory | up to 999 records on USB flash drive |
| Power supply | 100 to 240 V AC, 50/60 Hz |
| Safety | IEC/EN 61010-1:2010 |
| Operating temperature | -10 to +50 °C |
| Dimensions | 45.7 x 17.8 x 38.1 cm |
| Weight | 8.9 kg |
| Cables | 9.1 m, #1 AWG |
Part numbers
Show all part numbers (14)
8000-0221, 8000-0222, 8000-0016, 8000-0076, 8000-0147, 8000-0152, 8000-0153, 8000-0171, 8000-0172, 8000-0201, AUTO-OHM 200 S4 basic, S4 DG, S4 PR, S4 PRDG
Request a price and lead time
Micro-Ohmmeter AUTO-OHM 200 S4, DC, 200 A, for Circuit Breaker Contacts. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can contact resistance be measured on breakers earthed on both sides?
Yes, in the S4 DG and S4 PRDG versions with the dual ground option.
What is the measurement resolution?
0.1 µΩ in the range up to 999.9 µΩ at currents above 5 A.
Which standards does the unit meet?
The standards for contact resistance testing, EMC and safety are listed in the specification table.