ATRT-03 S2 Three-Phase Ratio Tester for Transformers, 100 V, with LTC Control

A third generation automatic three-phase tester for transformer turns ratio, used at substations. It recognises 130 types of three-phase transformer, measures the ratio, excitation current and phase angle, and controls on-load tap changer switching.

Type
automatic three-phase ratio tester for transformers
Test standard
C57.12.90 (ANSI/IEEE)
Ratio range
0.8 to 15,000:1
Error at 8 V
0.8 to 1,000 (±0.08%), 1,001 to 4,000 (±0.1%), 4,001 to 15,000 (±0.25%)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ATRT-03 S2 is used to test transformers directly in utility substations. Its housing is rugged and light, so the instrument is portable. It determines the turns ratio by the IEEE C57.12.90 method: an excitation voltage is applied to the primary winding, the induced voltage of the secondary winding is measured, and the ratio is calculated from the two readings.

An automatic circuit recognition function identifies 130 types of three-phase transformer according to ANSI, CEI/IEC and Australian standards. The instrument calculates the nominal ratio from the nameplate data and reports the percentage error between the measured and calculated values. The turns ratio, excitation current and phase angle appear on a large LCD screen.

Three test voltages are available: 8 V at 1 A, 40 V at 0.2 A and 100 V at 0.1 A. The ratio range is 0.8 to 15,000. At 40 V and 100 V the accuracy is ±0.05% from 0.8 to 1,000, ±0.1% from 1,001 to 4,000 and ±0.2% from 4,001 to 15,000, while at 8 V it is ±0.08%, ±0.1% and ±0.25% respectively. Phase angle is read from 0 to 360 degrees to within ±0.2 degree, and excitation current from 0 to 1 A.

A tap changer control contact rated at 240 V AC and 2 A switches the taps during successive measurements. Memory holds 112 complete test records, each with up to 99 readings, plus 128 test plans, and plans can be loaded from a PC over RS-232C or USB, or from a USB flash drive. Up to 999 records can be written to a flash drive. A 4.5-inch thermal printer is available as an option, and PC analysis software is included.

The unit runs from a 100 to 240 V AC supply at 50/60 Hz. It measures 45.7 x 17.8 x 38.1 cm and weighs 9.0 kg. Operating temperature is -10 to 50 °C and storage is -30 to 70 °C. Safety is designed to UL 61010A-1 requirements and Canadian CSA requirements. The cable set includes 15-foot single-phase and three-phase leads, a 25-foot extension, a safety ground, USB and RS-232C cables and a bag. Before the leads are connected, the instrument is earthed to the substation loop, and the transformer must be disconnected and isolated.

Technical specifications

Typeautomatic three-phase ratio tester for transformers
Test standardC57.12.90 (ANSI/IEEE)
Ratio range0.8 to 15,000:1
Error at 8 V0.8 to 1,000 (±0.08%), 1,001 to 4,000 (±0.1%), 4,001 to 15,000 (±0.25%)
Error at 40 and 100 V0.8 to 1,000 (±0.05%), 1,001 to 4,000 (±0.1%), 4,001 to 15,000 (±0.2%)
Test voltages8 V AC at 1 A, 40 V AC at 0.2 A, 100 V AC at 0.1 A
Excitation current0 to 1 A, ±2% of reading (±1 mA)
Phase angle0 to 360 degrees, accuracy ±0.2 degree (±1 digit)
Transformer connections130 types of three-phase transformer
LTC contact240 V AC, 2 A
Displaybacklit LCD, 64 x 128 dots
Printer4.5-inch thermal printer (optional)
InterfacesRS-232C, USB, USB flash drive port
Internal memory112 records of up to 99 readings, 128 test plans
External memoryup to 999 records on USB flash drive
Power supply100 to 240 V AC, 50/60 Hz
Operating temperature-10 to 50 °C
Dimensions45.7 x 17.8 x 38.1 cm
Weight9.0 kg

Part numbers

Show all part numbers (3)

9003-UC, 9003-PR, 9003-SC

Request a price and lead time

ATRT-03 S2 Three-Phase Ratio Tester for Transformers, 100 V, with LTC Control. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many transformer types can the instrument recognise?

It recognises 130 types of three-phase transformer, according to ANSI, CEI/IEC and Australian standards.

Can the unit switch an on-load tap changer?

Yes, the tap changer control contact is rated at 240 V AC and 2 A.

What is the highest accuracy?

±0.05% for ratios from 0.8 to 1,000 at a test voltage of 40 V or 100 V.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides