ATRT-01B S3 Transformer Ratio Tester, Single Phase, Mains or Battery Powered
An automatic tester for transformer turns ratio on one phase, powered from a 90 to 240 V AC mains supply or from a sealed lead-acid battery. It follows ANSI/IEEE C57.12.90 over a range of 0.8 to 15,000 and runs for up to 4 hours continuously on one charge.
- Type
- automatic transformer ratio tester, single phase
- Test standard
- ANSI/IEEE C57.12.90
- Ratio range
- 0.8 to 15,000 (five-digit resolution)
- Accuracy at 40 V
- 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 1% from 4,000 to 15,000
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ATRT-01B S3 is intended for field testing of power transformers, current and potential transformers and voltage regulators where a convenient mains connection is not available. This fourth generation, microprocessor based instrument runs from mains AC or from its built-in sealed lead-acid battery, which provides up to 4 hours of continuous operation per charge.
The turns ratio is measured to the ANSI/IEEE C57.12.90 method, with the unit reading the voltages across the windings of an unloaded transformer. The measuring circuit configures itself before each reading. The test voltage can be set to 4 V or 40 V AC, delivering 300 mA or 70 mA respectively, which suits different transformer types.
The ratio range is 0.8 to 15,000 with five-digit resolution. At 40 V, accuracy is 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999 and 1% from 4,000 to 15,000. The instrument also calculates the ratio error as a percentage, shows winding polarity, and measures phase angle from 0 to 360 degrees to ±0.2 degree and excitation current from 0 to 2 A to 2% of reading, plus or minus 1 mA.
Results appear on a backlit 128 x 64 pixel LCD that stays legible in direct sunlight. The unit stores 128 records of 33 readings internally, and up to 999 test records can be written to a USB flash drive. An RS-232C port connects it to a computer running the analysis software for Windows, which is supplied with the unit.
Housing dimensions are 30.4 by 25.4 by 20.3 cm and the weight is 4.3 kg. The unit operates from -10 to 50 °C and up to 90% humidity at 40 °C without condensation, at altitudes up to 2000 m. The design meets CSA-C22.2 and UL 61010A-1 standards, as well as IEC 61010 (1995). A 4.6 m single-phase cable, a power cord and a cable bag are included, and a transportation case is optional. The mains-only ATRT-01 S3 weighs 3.6 kg and uses the same method and test voltages.
Technical specifications
| Type | automatic transformer ratio tester, single phase |
|---|---|
| Test standard | ANSI/IEEE C57.12.90 |
| Ratio range | 0.8 to 15,000 (five-digit resolution) |
| Accuracy at 40 V | 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 1% from 4,000 to 15,000 |
| Accuracy at 4 V | 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 2% from 4,000 to 15,000 |
| Test voltage | 4 V AC at 300 mA, 40 V AC at 70 mA |
| Phase angle | 0 to 360 degrees, accuracy ±0.2 degree (±1 digit) |
| Excitation current | 0 to 2 A, accuracy 2% of reading (±1 mA) |
| Display | backlit LCD, 128 x 64 pixels |
| Interface | RS-232C |
| Internal memory | 128 records of 33 readings |
| External memory | up to 999 records on USB flash drive |
| Mains power | 90 to 240 V AC, 50/60 Hz |
| Battery | sealed lead-acid, up to 4 hours continuous operation |
| Operating temperature | -10 to 50 °C |
| Humidity | 90% RH at 40 °C, non-condensing |
| Dimensions | 30.4 by 25.4 by 20.3 cm |
| Weight | 4.3 kg |
| Safety | CSA-C22.2, UL 61010A-1, IEC 61010 (1995) |
Part numbers
Show all part numbers (4)
9036-UC, 8000-0006, 8000-0200, 8000-0112
Request a price and lead time
ATRT-01B S3 Transformer Ratio Tester, Single Phase, Mains or Battery Powered. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How long does the battery last?
The battery gives up to 4 hours of continuous operation per charge.
What test voltages and currents are available?
4 V AC at 300 mA and 40 V AC at 70 mA.
Can the unit be connected to a computer?
Yes, through the RS-232C interface, and the transformer analysis software for PC is included with the unit.