ATRT-01 S3 Automatic Transformer Ratio Tester, Single Phase, 4 and 40 V AC
A fourth generation, microprocessor based automatic tester for transformer turns ratio on one phase. It measures to IEEE C57.12.90 across a range of 0.8 to 15,000 and displays polarity, phase angle and excitation current.
- Type
- automatic transformer ratio tester, single phase
- Test standard
- C57.12.90 (ANSI/IEEE)
- Ratio range
- 0.8 to 15,000 (five-digit resolution)
- Accuracy at 40 V
- 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 1% from 4,000 to 15,000
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ATRT-01 S3 is used to check power transformers, current and potential transformers, and voltage regulators. It works either on its own or under computer control, calculates the turns ratio error as a percentage, and shows winding polarity as in-phase or out-of-phase, along with the phase angle and excitation current.
The ratio is measured to the IEEE C57.12.90 method, in which the unit reads the voltages on the windings of an unloaded transformer. The measuring circuit configures itself before every reading. Two test voltages, 4 V and 40 V AC, allow transformers of different types to be tested, with test currents of 1.0 A at 4 V and 0.6 A at 40 V.
The measuring range runs from 0.8 to 15,000, with five-digit resolution. At 40 V the accuracy is 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999 and 1% from 4,000 to 15,000, while at 4 V the top range is accurate to 2%. Phase angle is read from 0 to 360 degrees to within ±0.2 degree, and excitation current from 0 to 2 A to 2% of reading, plus or minus 1 mA.
The display is a backlit 128 x 64 pixel LCD, readable in direct sunlight and in low light. Internal memory holds 128 records of 33 readings each, and up to 999 test records can be saved to a USB flash drive. An RS-232C interface connects to a PC, and the transformer analysis software is included.
Mains supply is 120 or 240 V AC, selectable, at 50/60 Hz. The unit measures 30.4 x 25.4 x 20.3 cm and weighs 3.6 kg. It operates from -10 to 50 °C and withstands 90% humidity at 40 °C without condensation, at altitudes up to 2000 m. Each unit ships with a 4.6 m single-phase cable, a power cord and a cable bag, and a transport case is available as an option. The battery version, ATRT-01B S3, is the variant for field use away from mains.
Technical specifications
| Type | automatic transformer ratio tester, single phase |
|---|---|
| Test standard | C57.12.90 (ANSI/IEEE) |
| Ratio range | 0.8 to 15,000 (five-digit resolution) |
| Accuracy at 40 V | 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 1% from 4,000 to 15,000 |
| Accuracy at 4 V | 0.1% from 0.8 to 1,999, 0.25% from 2,000 to 3,999, 2% from 4,000 to 15,000 |
| Test voltage | 4 V AC at 1.0 A, 40 V AC at 0.6 A |
| Phase angle | 0 to 360 degrees, accuracy ±0.2 degree (±1 digit) |
| Polarity | in-phase or out-of-phase indication |
| Excitation current | 0 to 2 A, accuracy 2% of reading (±1 mA) |
| Display | backlit LCD, 128 x 64 pixels |
| Interface | RS-232C |
| Internal memory | 128 records of 33 readings |
| External memory | up to 999 records on USB flash drive |
| Power supply | 120 or 240 V AC, selectable, 50/60 Hz |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Humidity | 90% RH at 40 °C, non-condensing |
| Dimensions | 30.4 x 25.4 x 20.3 cm |
| Weight | 3.6 kg |
Part numbers
Show all part numbers (4)
9023-UC, 8000-0006, 8000-0200, 8000-0112
Request a price and lead time
ATRT-01 S3 Automatic Transformer Ratio Tester, Single Phase, 4 and 40 V AC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the S3 differ from the ATRT-01B S3?
The ATRT-01 S3 runs on mains power only, while the ATRT-01B S3 adds a battery and lower test currents.
What is the accuracy at 40 V?
0.1% for ratios from 0.8 to 1,999, 0.25% from 2,000 to 3,999 and 1% from 4,000 to 15,000.
How many test records can the unit store?
128 records of 33 readings in internal memory, and up to 999 test records on a USB flash drive.
Similar equipment from other manufacturers