Accelerated Ageing Test Systems for Dielectrics, 500 Hz, up to 110 kV and 1050 kVA

These systems age dielectrics by applying an electric field for tests to HD 605 S2 and ICEA S-94-649-2004. The typical frequency is 500 Hz, or alternatively 1000 Hz, smaller units run up to 3000 Hz, and the range spans 35 kV and 50 kVA to 110 kV and 1050 kVA.

Purpose
accelerated ageing of dielectrics by applying an electric field
Standards
HD 605 S2 and ICEA S-94-649-2004
Frequency
500 Hz, or 1000 Hz, smaller systems up to 3000 Hz
Resonant systems
up to 50 kVA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The systems are used for life testing of insulation on cables, gas-insulated switchgear (GIS), switchgear and insulating materials. Two types are offered. Systems up to 50 kVA are built as resonant units, while transformer-based systems work together with high voltage compensation reactors, which raise the power of the installation considerably.

The core is a solid-state frequency converter designed specifically for high voltage testing. The supply is three-phase, so the load is spread evenly across the phases. The converter uses fast-switching water-cooled IGBTs, and the high switching frequency gives a near-sinusoidal waveform with very little distortion, along with high output power for testing many specimens at once. The same converter can run at 500 Hz, or at 1000 Hz, with a modest drop in power, and a low-loss sine filter sits between the converter and the step-up transformer.

Compensation reactors have a core of anisotropic electrical steel with copper windings. A distributed air gap keeps losses low and gives a high quality factor. The closed magnetic circuit limits stray fields and induction heating in nearby metal parts, a problem typical of reactors with open or air cores. The reactors are oil-filled in stainless steel tanks, suitable for indoor or outdoor sites, and a weatherproof version is available. Taps allow several voltage classes to be tested and compensation to be fine-tuned. Reactors can be paralleled to extend an installed system, or connected in series on insulating supports to double the test voltage range.

All systems have full computer control with automatic voltage regulation and data logging. An industrial HMI with Ethernet supports remote operation, and an interface for laboratory SCADA systems or databases is available as an option.

The 500 Hz range includes the RTS8TC35-50-500X resonant model rated 35 kV and 50 kVA, and the 6TC transformer models for 55 or 110 kV at 250, 450, 650, 850 and 1050 kVA, with between zero and four reactors. Load capacitance runs from 6.7 to 110 nF depending on the model.

Technical specifications

Purposeaccelerated ageing of dielectrics by applying an electric field
StandardsHD 605 S2 and ICEA S-94-649-2004
Frequency500 Hz, or 1000 Hz, smaller systems up to 3000 Hz
Resonant systemsup to 50 kVA
Supplythree-phase
RTS8TC35-50-500X35 kV, 50 kVA, no reactors, load 13 nF
6TC55-250-500X55 kV, 250 kVA, no reactors, load 26 nF
6TC110-250-500X110 kV, 250 kVA, no reactors, load 6.7 nF
6TC55-450-500X55 kV, 450 kVA, 1 reactor, load 47 nF
6TC110-450-500X110 kV, 450 kVA, 1 reactor, load 12 nF
6TC55-650-500X55 kV, 650 kVA, 2 reactors, load 68 nF
6TC110-650-500X110 kV, 650 kVA, 2 reactors, load 17 nF
6TC55-850-500X55 kV, 850 kVA, 3 reactors, load 89 nF
6TC110-850-500X110 kV, 850 kVA, 3 reactors, load 22 nF
6TC55-1050-500X55 kV, 1050 kVA, 4 reactors, load 110 nF
6TC110-1050-500X110 kV, 1050 kVA, 4 reactors, load 27 nF

Part numbers

Show all part numbers (11)

6TC110-1050-500X, 6TC55-1050-500X, 6TC110-850-500X, 6TC55-850-500X, 6TC110-650-500X, 6TC55-650-500X, 6TC110-450-500X, 6TC55-450-500X, 6TC110-250-500X, 6TC55-250-500X, RTS8TC35-50-500X

Request a price and lead time

Accelerated Ageing Test Systems for Dielectrics, 500 Hz, up to 110 kV and 1050 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does a resonant system differ from a transformer system?

Resonant systems are used at low power, up to 50 kVA. Transformer systems work with compensation reactors and reach 1050 kVA in the 500 Hz range.

Can the power of an installed system be increased?

Yes. Compensation reactors can be paralleled to extend the system, and series connection on insulating supports doubles the voltage range.

Can the system run at a different frequency?

The same converter can run at 500 or 1000 Hz with some reduction in power, and smaller systems are built for up to 3000 Hz.