8TX variable frequency resonant test systems, tank type, 160–265 kV

Variable frequency resonant test systems of the 8TX series, with reactors in a steel tank, for on-site AC testing of cables, capacitors and rotating machines. Models rated at 160, 180 and 265 kV and 6000, 13000 or 22000 kVA operate across the recommended IEC band of 20 to 300 Hz.

Voltage
160 / 180 / 265 kV (160 kV tap on 8TX265)
Power
6000 / 13000 / 22000 kVA
Frequency range
20 – 300 Hz
Load capacitance 8TX180-22000
3.60 µF (30 Hz), 2.16 µF (50 Hz), 1.80 µF (60 Hz)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 8TX series is designed mainly for on-site testing of power cables, capacitors and rotating machines. Other capacitive loads with low losses can also be tested, including GIS, generator windings, motors and dry insulators. For their rating the systems are light and transportable, and they can be set up quickly. Stationary versions for factories and laboratories are available.

The system is tuned to resonance by changing the frequency. The reactor has a fixed inductance, so the frequency is chosen until the reactor's inductive reactance matches the capacitive reactance of the load. Only the active losses of the circuit are then drawn from the mains, so a higher quality factor Q means less input power. The output is a pure sinusoid, and the system runs from a symmetrical three-phase supply.

The reactor coils sit in oil inside an earthed, painted steel tank. The radially laminated cores are wrapped in copper windings chosen for low losses and high Q. The tank can carry several output taps through a changeover switch or several bushings, and paralleling reactors gives high currents. Operation is series resonant, there are no moving internal parts, and maintenance is hardly needed.

The range comprises five models. The 8TX160-13000 gives 160 kV at 13000 kVA in a 2.54 × 2.92 × 2.58 m enclosure weighing 22.5 t, while the 8TX180-22000 gives 180 kV at 22000 kVA, measures 2.54 × 2.32 × 2.58 m and weighs 26.8 t. The 8TX265-6000 reaches 265 kV with a 160 kV tap at 6000 kVA and measures 7.0 × 3.5 × 2.2 m, weighing 16.4 t. The 8TX265-13000 and 8TX265-22000 provide 265/160 kV at 13000 and 22000 kVA. As an example, the 8TX180-22000 works with 3.60 µF at 30 Hz, 2.16 µF at 50 Hz and 1.80 µF at 60 Hz, excluding divider capacitance.

Each system runs in 1 hour on and 1 hour off cycles, with three or six cycles per day depending on the model. The control cabinet measures 2159 × 965 × 2032 mm and weighs 1451 kg, and the console measures 1118 × 762 × 813 mm and weighs 79 kg. The systems meet IEC 60517 and IEC 62271-203 and the recommended IEC frequency band of 20 to 300 Hz, and other configurations are built to order.

Technical specifications

Voltage160 / 180 / 265 kV (160 kV tap on 8TX265)
Power6000 / 13000 / 22000 kVA
Frequency range20 – 300 Hz
Load capacitance 8TX180-220003.60 µF (30 Hz), 2.16 µF (50 Hz), 1.80 µF (60 Hz)
Load capacitance 8TX265-22000, 160 kV tap4.55 µF (30 Hz)
Duty cycle1 h on / 1 h off, 3 or 6 cycles per day
Reactor dimensionsfrom 2.54 × 2.32 × 2.58 m to 7.0 × 3.5 × 2.2 m
Reactor weight16.4 – 31.7 t
Power cabinet2159 × 965 × 2032 mm, 1451 kg
Control console1118 × 762 × 813 mm, 79 kg
Constructionearthed steel tank, oil insulation
Output voltagepure sinusoidal
StandardsIEC 60517, IEC 62271-203

Part numbers

Show all part numbers (5)

8TX160-13000, 8TX180-22000, 8TX265-6000, 8TX265-13000, 8TX265-22000

Request a price and lead time

8TX variable frequency resonant test systems, tank type, 160–265 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which objects is the 8TX series suited to?

Its main use is on-site testing of cables, capacitors and rotating machines. Other capacitive objects with low losses can be tested as well.

What does the second 160 kV tap on the 8TX265 models give?

At the 160 kV tap the system handles a larger capacitance. For example the 8TX265-22000 reaches 4.55 µF at 30 Hz, compared with 2.69 µF on the 265 kV tap.

How many test cycles per day does the system allow?

The duty cycle is 1 hour on and 1 hour off. The 8TX265-6000 and 8TX265-13000 allow six cycles per day, and the other models allow three.