6CP and 6CB AC dielectric test sets for field and laboratory use, 15–200 kV

Portable high voltage AC test sets in the 6CP and 6CB series, rated from 15 kV to 200 kV AC for laboratory and site work. The control cabinet and regulator sit apart from the high-voltage section, which holds an oil-filled transformer with low partial discharge output.

Rated voltage
15–200 kV AC
Series
6CP (digital meters), 6CB (7-inch touch display)
High-voltage transformer
oil insulated, cylindrical housing
Output electrode
aluminium, corona-free

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Designed for AC dielectric testing of cables, switchgear, generators, motors, insulating materials, circuit breakers, reclosers, transformers, vacuum interrupters and protective devices, the 6CP and 6CB series are rated from 15 kV to 200 kV AC. Examples include the 6CP100/50-7.5, 6CP200/100-10 and 6CB30/15-3. The units are light and rugged, built for years of service both in the laboratory and out on site.

Each unit is made of a combined control and regulator cabinet plus a separate high-voltage section. The high-voltage section has an oil-filled transformer inside an insulating cylindrical housing on a steel base. The output is fitted with an aluminium corona-free screening electrode, which keeps the partial discharge level at the output low. A guard mode diverts stray capacitive currents so that the leakage current of the test object is read accurately.

The 6CP models have digital multi-range LCD meters and manual voltage adjustment. Overcurrent protection is adjustable from 10 % to 110 % of rated current, and both the instruments and the relays are protected against slow and fast transients. A digital timer with an audible alarm is fitted. The 6CB models have a 7-inch colour touch display, automatic or manual voltage control, a USB port for data logging, PC control over WiFi with separate software, memory voltmeters for breakdown and peak voltage, duration and dwell timers, a programmable voltage rise rate in V/s and a current cut-off threshold.

Both series have an input circuit breaker, an external signal circuit for a flashing lamp, high voltage on and off buttons with indicators, a latching emergency stop, an interlock that blocks start-up from any non-zero setting and external interlock terminals. Each unit is delivered ready to run with all supply and connection cables, together with a user manual and a calibration certificate.

Ambient conditions run from 10 to 40 °C, indoors or outdoors in dry weather, with relative humidity up to 95 % and no condensation, at altitudes up to 1000 m. Optional extras include flashing or red-green lamps, a foot-operated safety switch with a 20’ (6 m) cable, a hand-held safety switch with a 10’ (3 m) cable, mains filters, an earthing rod, a cover, a hand trolley for the 30 kV and 50 kV models, a heavy-duty trolley, an aluminium transformer cover, a tank lifting kit, partial discharge certification and ISO17025 calibration.

Technical specifications

Rated voltage15–200 kV AC
Series6CP (digital meters), 6CB (7-inch touch display)
High-voltage transformeroil insulated, cylindrical housing
Output electrodealuminium, corona-free
Overload protection 6CP10–110% of rated current
Adjustment 6CBautomatic or manual, rise rate in V/s
Interfaces 6CBUSB, WiFi
Guard modeyes
Ambient temperature10–40 °C
Relative humidity<95% non-condensing
Altitude<1000 m
CalibrationISO17025 on request

Part numbers

Show all part numbers (3)

6CP100/50-7.5, 6CP200/100-10, 6CB30/15-3

Request a price and lead time

6CP and 6CB AC dielectric test sets for field and laboratory use, 15–200 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the 6CP and 6CB series differ?

The 6CP has digital multi-range meters and manual voltage control, while the 6CB has a 7-inch touch display, automatic regulation, USB data logging and a memory voltmeter for breakdown voltage.

Is the set suitable for partial discharge measurement?

The high-voltage section with an oil-filled transformer and corona-free screening electrode has a low partial discharge level, and partial discharge certification is available on request.

What are the operating conditions on site?

From 10 to 40 °C, in dry weather outdoors, with humidity up to 95 % non-condensing and altitudes up to 1000 m.