660-10P two-section vacuum interrupter test set, 0 to 60 kV AC, 10 mA
A two-section variable voltage test set, the 660-10P, used for testing vacuum interrupters, circuit breakers and switchgear. It has automatic voltage rise with selectable speed and a memory voltmeter that records the breakdown voltage.
- Output voltage
- approx. 0–60 kV AC
- Output current
- 10 mA
- Supply
- 110–120 V, 6 A or 220–240 V, 3 A
- Mains frequency
- 50/60 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 660-10P is chiefly used for testing vacuum interrupters with variable high voltage. It is also used to test circuit breakers, switchgear, reclosers and other equipment. The unit is light and rugged, made for years of use on site, and its digital meters are easy to read. Assembly and preparation for use are simple.
Output is approximately 0 to 60 kV AC at 10 mA. Mains supply is 110–120 V at 6 A or 220–240 V at 3 A, 50 or 60 Hz. The digital voltmeter reads 0 to 60 kV and the ammeter reads 0 to 10 mA, with an accuracy of 0.8 % of reading plus 0.2 % of full scale.
The set comes in two sections: a control unit and a high-voltage tank. The control unit measures 381 × 267 × 330 mm and weighs 14 kg, while the high-voltage tank measures 356 × 356 × 432 mm and weighs 30 kg. All control, supply and output cables are included, and there is room to store them.
Voltage is raised by automatic control with a selectable rise rate. The output voltmeter has a memory function that holds the breakdown voltage of the chamber. A digital timer measures the test duration. Protection consists of high voltage on and off buttons with indicators, an interlock that blocks start-up from any non-zero setting, transient protection for instruments and relays, an output overload indicator with reset button and external interlock terminals.
The smaller 640-0.4P is a single-unit design with manual regulation and an output of approximately 0 to 40 kV. The choice between them depends on the voltage class of the chambers under test. Operating conditions are 10 to 40 °C, indoors or outdoors in dry weather, with humidity up to 95 % without condensation and altitudes up to 1000 m. Cables of other lengths are available on request, and an operating and maintenance manual is supplied.
Technical specifications
| Output voltage | approx. 0–60 kV AC |
|---|---|
| Output current | 10 mA |
| Supply | 110–120 V, 6 A or 220–240 V, 3 A |
| Mains frequency | 50/60 Hz |
| Measurement accuracy | 0.8% of reading + 0.2% of full scale |
| Voltmeter range | 0–60 kV |
| Ammeter range | 0–10 mA |
| Construction | 2 sections |
| Control unit | 381 × 267 × 330 mm, 14 kg |
| High-voltage tank | 356 × 356 × 432 mm, 30 kg |
| Voltage adjustment | automatic, with selectable rise rate |
| Operating temperature | 10–40 °C |
| Relative humidity | <95% non-condensing |
| Altitude | <1000 m |
Part numbers
Show all part numbers (1)
660-10P
Request a price and lead time
660-10P two-section vacuum interrupter test set, 0 to 60 kV AC, 10 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the set record the breakdown voltage of a chamber?
Yes, the output voltmeter has a memory function that stores the breakdown voltage.
What do the two parts weigh?
The control unit weighs 14 kg and the high-voltage tank weighs 30 kg.
Are cables included?
Yes, all control, supply and output cables are included, and cables of other lengths are available on request.