International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

STB and STB-L Dry Wall Bushings with Condenser Grading, 40.5–252 kV

Oil-free and gas-free wall bushings that carry a high-voltage conductor through a substation wall or partition. The STB is the bushing on its own, while the STB-L has a current transformer built into the same body, saving space in the bay.

Highest voltage for equipment
40.5 / 72.5 / 126 / 252 kV
Current rating
100–3150 A
Frequency
50 Hz; 60 Hz
1 min power-frequency withstand
95 / 140 / 230 / 460 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Voltage grading inside the bushing comes from conductive foils embedded in a solid PTFE core. Over that core sits a silicone rubber housing, sealed against water and pollution, whose sheds give long creepage paths. Because silicone is hydrophobic, moisture beads into separate droplets instead of forming a film, which keeps leakage current down and limits flashover on wet, dirty sites. The fixing flange is part of the bushing; the conductor itself may be integral or supplied separately.

With no oil or SF6 in the insulation, there is nothing to leak if cantilever loads act on the flange, and no gas pressure or oil level to check during routine substation rounds.

Four voltage classes are listed: 40.5, 72.5, 126 and 252 kV highest system voltage, each with current ratings of 100–3150 A for 50 Hz or 60 Hz systems. One-minute power-frequency test levels are 95, 140, 230 and 460 kV, and lightning impulse levels 200, 325, 550 and 1050 kV peak. Partial discharge stays at or below 5 pC, tanδ does not exceed 0.004 at 10 kV and 1.05 Ur/√3, and the short-time withstand is 25 Ir for 1 s.

On the STB-L, the integral CT offers ratios from 100/1 to 2500/1 A or from 100/5 to 2500/5 A, burdens of 20–40 VA, between 1 and 6 secondary cores, metering classes 0.5, 0.5S, 0.2 or 0.2S and protection classes 10P or 5P.

Standard units work in ambient air between -45°C and +45°C at altitudes below 1000 m, and the specific creepage distance is 25–31 mm/kV; a dedicated design is available for higher sites. Production is ISO 9001 certified and the products follow IEC and IEEE standards.

Technical specifications

Highest voltage for equipment40.5 / 72.5 / 126 / 252 kV
Current rating100–3150 A
Frequency50 Hz; 60 Hz
1 min power-frequency withstand95 / 140 / 230 / 460 kV
Lightning impulse withstand200 / 325 / 550 / 1050 kV
Partial discharge≤ 5 pC
Dissipation factor (tanδ)≤ 0.004
Short-time current25 Ir, 1 s
InsulationPTFE with foils, silicone rubber sheds
Current transformer (STB-L)100–2500/1 A or 100–2500/5 A, 20–40 VA
Accuracy classes (STB-L)0.5, 0.5S, 0.2, 0.2S, 10P, 5P
Ambient temperature-45°C … +45°C
Altitudeup to 1000 m
Specific creepage distance25–31 mm/kV

Request a price and lead time

STB and STB-L Dry Wall Bushings with Condenser Grading, 40.5–252 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does the STB-L differ from the STB?

The STB-L houses a current transformer with ratios of 100–2500/1 A or 100–2500/5 A and up to 6 secondary cores; the STB is the bushing alone.

Does the insulation need routine maintenance?

No oil or gas is used, so there are no levels or pressures to monitor, and the hydrophobic silicone sheds cope with polluted atmospheres.

Can it be installed above 1000 m?

The standard design covers sites up to 1000 m; for higher altitudes the manufacturer offers a dedicated design on enquiry.