International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

STB-L Wall Bushing with Built-in Current Transformer, 40.5–252 kV

Where a high-voltage conductor passes through a building wall, the STB-L series puts the wall bushing and a toroidal current transformer into one compact unit. It suits substations rated 40.5–252 kV that need metering or protection signals at the wall entry.

Rated voltage, series
40.5–252 kV
Highest voltage, standard models
40.5; 72.5; 126 kV
Rated current, standard models
630; 1600; 2000~2500 A
Rated transformation ratio
100~2500/5 A or 100~2500/1 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Standard sizes cover highest equipment voltages of 40.5, 72.5 and 126 kV with rated currents of 630 A, 1600 A or 2000~2500 A, designated STB-L-40.5/630, STB-L-40.5/2000, STB-L-72.5/630, STB-L-72.5/1600, STB-L-126/630 and STB-L-126/2000~2500. Overall length and creepage distance grow with the voltage class, so a 126 kV unit is considerably longer than its 40.5 kV counterpart. Other dimensions are built to the customer's own specification.

The current transformer is a toroidal core fitted around the bushing body rather than a separate free-standing unit, which saves space in the switchroom and removes one set of primary connections. Between one and six secondary windings can be specified, each with a rated output of 20–40 VA.

Ratios are 100~2500/5 A or 100~2500/1 A at 50 Hz or 60 Hz. Metering cores come in accuracy classes 0.2S, 0.2, 0.5S and 0.5; protection cores in 5P or 10P with an accuracy limit factor of 5, 10, 15, 20, 30 or 40. Across the whole series the rated voltage extends from 40.5 kV up to 252 kV.

The standard design works in ambient temperatures from -50 °C to +45 °C at altitudes up to 1000 m above sea level; a special version is offered for higher sites. Specific creepage distance is 25 to 31 mm/kV. With an enquiry, state the voltage class, rated current, ratio, the number of secondary windings and the accuracy class required for each core.

Technical specifications

Rated voltage, series40.5–252 kV
Highest voltage, standard models40.5; 72.5; 126 kV
Rated current, standard models630; 1600; 2000~2500 A
Rated transformation ratio100~2500/5 A or 100~2500/1 A
Rated frequency50–60 Hz
Rated output20–40 VA
Metering accuracy classes0.2S; 0.2; 0.5S; 0.5
Protection accuracy classes5P; 10P
Accuracy limit factor5, 10, 15, 20, 30, 40
Secondary windings1–6
Ambient temperature-50 to +45 °C
Altitudeup to 1000 m
Specific creepage distance25–31 mm/kV

Request a price and lead time

STB-L Wall Bushing with Built-in Current Transformer, 40.5–252 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the STB-L be fitted above 1000 m?

The standard build is rated for altitudes up to 1000 m above sea level. For higher sites the manufacturer supplies a special design.

How many secondary cores can the built-in CT carry, and in which classes?

From one to six secondary windings, with metering classes 0.2S, 0.2, 0.5S or 0.5 and protection classes 5P or 10P at an accuracy limit factor between 5 and 40.

Which current ratings are covered by the standard models?

630 A, 1600 A and 2000~2500 A, at highest equipment voltages of 40.5, 72.5 or 126 kV. Non-standard sizes are made to specification.