SDC 095-008-W-920-00 Capacitor Bushing, Wall or Floor, 13.8 kV, 800 A, 95 kV BIL
The SDC bushing, part number 095-008-W-920-00, carries a conductor through a wall or floor with air on both sides. It is rated 13.8 kV and 800 A with a 95 kV BIL, has a creepage distance of 13.8 in outside, and its terminal is bottom connected with a 1 in ground shield.
- Type
- Solid dielectric capacitor bushing, wall or floor
- Voltage class
- 13.8 kV
- Rated current
- 800 A
- BIL
- 95 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
SDC series bushings (solid dielectric capacitor) are supplied both as new products for equipment manufacturers and as replacements of the same dimensions and connections. They suit power transformers, generator step-up transformers, oil circuit breakers, switchgear, wall and floor passages (air-to-air and oil-to-oil) and HVDC installations. The series covers voltages from 1 to 170 kV and currents up to 21500 A.
The body is a solid insulating mass of APG-02 cycloaliphatic epoxy compound, with ribs cast in one piece with it. The insulation is solid, with no oil, paper or porcelain. Inside are a capacitance graded core, a pocket for a current transformer with a ground shield, and a test tap on the flange. The series is made with bottom connection or with a draw-through conductor, and this item has a bottom connection.
Version 095-008-W-920-00 is for wall or floor use with air above and below the flange, rated 13.8 kV, 800 A and 95 kV BIL, with a 60 Hz dry withstand voltage of 34 kV. The minimum creepage distance is 13.8 in outside and 8.1 in inside, and the minimum strike distance is 6.9 in and 7.3 in respectively. The ground shield length is 1 in.
The aluminium flange has four 0.88 in holes on a 7.25 in bolt circle, and its outside diameter is 8.5 in. The top and bottom terminals are type 1-14 with silver plating, the rod diameter is 1.25 in and the effective terminal length is 2 in. The overall length is 22.6 in, with 11.91 in above the flange and 10.69 in below it, and the weight is 20 lb. The bushing can be installed in any position from vertical to horizontal, and it is made to IEEE C57.19.01, CSA C88.1 and IEC 60137. A test tap on the flange is used to check capacitance and dissipation factor during periodic tests.
Technical specifications
| Type | Solid dielectric capacitor bushing, wall or floor |
|---|---|
| Voltage class | 13.8 kV |
| Rated current | 800 A |
| BIL | 95 kV |
| Dry withstand voltage, 60 Hz | 34 kV |
| Medium above / below flange | Air / air |
| Creepage distance, outside / inside | 13.8 in / 8.1 in |
| Strike distance, outside / inside | 6.9 in / 7.3 in |
| Ground shield | 1 in |
| Insulation | APG-02, cycloaliphatic epoxy |
| Flange | Aluminium, 4 holes of 0.88 in on 7.25 in bolt circle |
| Terminals | 1-14, silver plated |
| Rod diameter | 1.25 in |
| Overall length | 22.6 in |
| Mounting position | Vertical to horizontal |
| Test tap | Yes |
| Weight | 20 lb |
| Standards | IEEE C57.19.01, CSA C88.1, IEC 60137 |
Part numbers
Show all part numbers (1)
095-008-W-920-00
Request a price and lead time
SDC 095-008-W-920-00 Capacitor Bushing, Wall or Floor, 13.8 kV, 800 A, 95 kV BIL. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the bushing be installed horizontally?
Yes, the permitted mounting position runs from vertical to horizontal.
Does the bushing contain oil?
No, the insulation is solid APG-02 epoxy, with no oil, paper or porcelain.
Which environment is this item designed for?
For wall or floor passages with air above and below the flange. The series also includes oil-to-oil versions.