BGCT Board Mounted Generator Bushing Current Transformer, 600 V Insulation Class
The BGCT is a board mounted bushing current transformer for generators, used for relaying and metering. It is assembled on a mounting board, so it can be placed into the installation as a finished assembly.
- Type
- Bushing current transformer for generators, board mounted
- Mounting
- On the high voltage generator bushing or on IPB
- Insulation class
- 600 V
- Application
- Relaying and metering
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The transformer is placed over the high voltage terminal bushing of a generator. As with other generator transformers of this type, it can be fitted over an isolated phase bus (IPB) in higher voltage systems, and it keeps its own 600 V insulation class. The mounting arrangement is made to suit any existing structure, and the unit is lighter than cast alternatives.
The BGCT is assembled on a mounting board, so it is put into position as a finished unit. The manufacturer offers pre-assembled packages of several cores. Coils can also be supplied separately, without the board, with terminals or flexible leads, where a mounting is already in place.
Each transformer is designed for the specific application and, where required, to match the characteristics of the transformer it replaces, so that protection does not need to be re-set. The core can have an air gap to limit residual magnetism and to influence behaviour in transient conditions. The windings can be provided with additional taps for testing. Conduit openings are threaded up to 1.5 in NPT, or non-threaded holes up to 52 mm are provided.
The rating factor is up to 1.0 at 55 °C ambient. Metering accuracy classes run from 0.15S to 0.6 under IEEE and from 0.2S to 0.5 under IEC, with burdens from B0.1 to B1.8 or from 2.5 to 45 VA. The dimensions and accuracy class depend on the transformation ratio, and only the single ratio (SR) version is offered.
Technical specifications
| Type | Bushing current transformer for generators, board mounted |
|---|---|
| Mounting | On the high voltage generator bushing or on IPB |
| Insulation class | 600 V |
| Application | Relaying and metering |
| Rating factor | Up to 1.0 at 55 °C |
| Accuracy class (IEEE) | 0.15S to 0.6 |
| Accuracy class (IEC) | 0.2S to 0.5 |
| Burdens | B0.1 to B1.8 / 2.5 to 45 VA |
| Ratio | Single ratio (SR) only |
| Supply form | On board, multi-core packages or separate coils |
| Coil leads without board | Terminals or flexible leads |
| Conduit openings | Threaded 1.5 in NPT, or holes up to 52 mm |
Request a price and lead time
BGCT Board Mounted Generator Bushing Current Transformer, 600 V Insulation Class. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the BGCT differ from the encapsulated EGCT?
The BGCT is assembled on a mounting board, while the EGCT is encapsulated. Coils of the BGCT can also be supplied without the board.
Can only the coils be ordered?
Yes, the coils are supplied without the board, with terminals or flexible leads.
Which accuracy classes are available?
From 0.15S to 0.6 under IEEE and from 0.2S to 0.5 under IEC. The achievable class depends on the transformation ratio.