DBCT Internally Mounted Dry Type Bushing Current Transformer, Primary Over 8000 A
The DBCT is a dry bushing current transformer mounted on the grounded collar of a high voltage power circuit breaker bushing, under an outer cover or inside a weather-tight cabinet. It has low leakage flux and very high short circuit withstand capability.
- Type
- Dry bushing current transformer, internally mounted
- Mounting
- On the grounded flange of a power breaker bushing, in a cabinet or MC switchgear compartment
- Application
- Relaying and metering
- Primary current
- Over 8000 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The transformer is installed along the grounded part of the high voltage bushing of a power circuit breaker, where an outer cover encloses it. It can also be mounted inside a weather-tight cabinet or in the compartment of metal-clad switchgear (MC switchgear). The design is dry, with no oil and no casting, and protection from the environment is provided by the cover or cabinet.
The design gives low leakage flux and very high short circuit withstand capability. Each unit is engineered to fit over the shank of a specific bushing and, where required, to match the characteristics of the transformer it replaces. Primary currents above 8000 A are supported.
The secondary terminals are made as terminal blocks or flexible leads. The core can have an air gap to limit residual magnetism and to influence behaviour in transient conditions. Air core linear couplers are also available. The windings are supplied as single ratio (SR), dual ratio (DR) or multi ratio (MR).
The rating factor is up to 5.0 at an ambient temperature of 55 °C. Accuracy classes run from 0.15S to 2.4 and from 0.2S to 5.0, with burdens from B0.1 to B1.8 or from 2.5 to 45 VA. The dimensions and accuracy class depend on the transformation ratio, and the unit is used for relaying and metering.
For selection, drawings of the bushing and the grounded flange of the breaker, the free height available for the transformer, the primary current, the winding arrangement, accuracy classes and burdens, and the nameplate data of the transformer being replaced are required.
Technical specifications
| Type | Dry bushing current transformer, internally mounted |
|---|---|
| Mounting | On the grounded flange of a power breaker bushing, in a cabinet or MC switchgear compartment |
| Application | Relaying and metering |
| Primary current | Over 8000 A |
| Rating factor | Up to 5.0 at 55 °C |
| Accuracy class | 0.15S to 2.4 / 0.2S to 5.0 |
| Burdens | B0.1 to B1.8 / 2.5 to 45 VA |
| Windings | SR, DR or MR |
| Secondary terminals | Terminal blocks or flexible leads |
| Options | Gapped core, air core linear couplers |
Request a price and lead time
DBCT Internally Mounted Dry Type Bushing Current Transformer, Primary Over 8000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Where is the DBCT installed?
On the grounded flange of a high voltage power breaker bushing, under an outer cover, in a weather-tight cabinet or in an MC switchgear compartment.
What primary currents is the DBCT made for?
Primary currents above 8000 A. The dimensions and accuracy class depend on the transformation ratio.
What secondary terminals are available?
Terminal blocks or flexible leads, with windings in a single, dual or multi ratio arrangement.
Similar equipment from other manufacturers