POC 88 condenser bushing B-88013-200-70, 69 kV, 1200 A, air to oil
B-88013-200-70 is a POC 88 series condenser bushing rated 69 kV for power transformers and oil circuit breakers, in the air to oil design. The insulating core is made of oil-impregnated paper inside an external porcelain housing, and the connection is made through a drawlead or a bottom terminal.
- Model
- B-88013-200-70
- Series
- POC 88
- Type
- condenser bushing, air to oil
- Voltage class
- 69 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The POC 88 series bushing, model B-88013-200-70, is installed on the tank of a power transformer or an oil circuit breaker. Its upper section above the flange operates in air, while the lower section sits immersed in oil. The unit is rated 69 kV, with a BIL of 350 kV (lightning impulse insulation level) and a rated current of 400/1200 A. The connection to the winding lead can be made with a drawlead or through the bottom terminal.
The insulating core is wound from paper impregnated with oil, and the capacitive grading of the field is achieved with foil layers inside the insulation. Outside, a grey porcelain housing encloses the core, and the internal volume is filled with oil. The design is rated for increased seismic loads and meets IEEE requirements. A test tap allows the capacitance and dielectric loss tangent to be measured in service without dismantling the unit.
The minimum creepage distance is 54 in and the minimum strike distance is 24 in. The minimum oil immersion level is 21.00 in, and the ground shield is of the same length. The length above the flange is 35.06 in and below the flange 44.06 in, the overall height is 79.12 in, the width is 9.38 in and the weight is 190 lb. The drawlead above the flange measures 31.12 in.
The aluminium flange has an outside diameter of 11 in and six mounting holes of 0.88 in diameter on a 9.25 in bolt circle, with a sealing surface of 8.25 in outside diameter. The bottom terminal is a two-hole NEMA pad, and the top terminal is a threaded 1 1/2-12 silver-plated terminal with an effective length of 2.50 in. The mounting position is vertical. Before installation, confirm that the oil level in the equipment tank will not fall below the minimum immersion level of the bushing.
Technical specifications
| Model | B-88013-200-70 |
|---|---|
| Series | POC 88 |
| Type | condenser bushing, air to oil |
| Voltage class | 69 kV |
| BIL | 350 kV |
| Rated current | 400/1200 A |
| Minimum creepage distance | 54 in |
| Minimum strike distance | 24 in |
| Minimum oil immersion level | 21.00 in |
| Length above / below flange | 35.06 in / 44.06 in |
| Height | 79.12 in |
| Flange outside diameter | 11 in |
| Flange holes | 6 × 0.88 in on a 9.25 in circle |
| Bottom terminal | NEMA pad, 2 holes |
| Top terminal | threaded 1 1/2-12, silver plated |
| Insulation | oil-impregnated paper; porcelain |
| Flange material | aluminium |
| Test tap | yes |
| Weight | 190 lb |
Part numbers
Show all part numbers (1)
B-88013-200-70
Request a price and lead time
POC 88 condenser bushing B-88013-200-70, 69 kV, 1200 A, air to oil. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the rated current of 400/1200 A mean?
It is the rated current given in the specification of the bushing, with the highest value at 1200 A. The bushing allows connection with a drawlead or through the bottom terminal.
What is the minimum oil immersion depth?
21.00 in. The oil level in the tank should not fall below this level.
Does the bushing have a test tap?
Yes. It allows capacitance and dielectric losses to be measured in service.