OBCT internally mounted oil-type bushing current transformer, primary current over 8000 A
The OBCT is a current transformer fitted inside the tank of a power transformer alongside the bushing shank, or within power circuit breakers and voltage regulators. Each unit is built to suit a specific bushing and can reproduce the characteristics of an existing current transformer, for relaying and metering duties.
- Type
- bushing current transformer, oil-filled design
- Installation location
- power transformer tank, power circuit breakers, voltage regulators
- Primary current
- over 8000 A
- Voltage class
- 600 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
OBCT units are oil-type bushing current transformers that operate immersed in oil. They can be fitted inside the tank of a power transformer alongside the bushing shank, or inside power circuit breakers and voltage regulators. The secondary circuits serve relaying protection and energy metering. The voltage class of the unit is 600 V, and it suits installations operating at higher system voltages.
The design has low leakage flux and withstands high short-circuit currents. The cores are built with an air gap, which limits residual magnetism and improves behaviour during transient conditions. Where a linear response is needed, the assembly includes air core linear couplers with no ferromagnetic core. Windings are offered as single ratio (SR), dual ratio (DR) or multi ratio (MR), and the chosen arrangement sets the dimensions and the accuracy class.
Every unit is manufactured around the shank of one particular bushing. When an existing current transformer is being replaced, the new unit can reproduce its characteristics, so protection and metering settings do not have to be changed. The primary current can exceed 8000 A, and the rating factor reaches up to 2.0 at a 95 °C ambient temperature.
Metering accuracy classes run from 0.15S to 2.4 and from 0.2S to 5.0, and the secondary burden ranges from B0.1 to B1.8, or from 2.5 to 45 VA, depending on the designation system used. To make a selection, the bushing data and the mounting location are needed: shank diameter and length, required ratio, accuracy class, secondary burden and winding arrangement. Fitting takes place during repair or manufacture of the main apparatus, while the bushing shank is accessible.
Technical specifications
| Type | bushing current transformer, oil-filled design |
|---|---|
| Installation location | power transformer tank, power circuit breakers, voltage regulators |
| Primary current | over 8000 A |
| Voltage class | 600 V |
| Rating factor | up to 2.0 at 95 °C ambient |
| Metering accuracy classes | 0.15S to 2.4 / 0.2S to 5.0 |
| Secondary burden | B0.1 to B1.8 / 2.5 to 45 VA |
| Winding arrangements | SR, DR, MR |
| Core | gapped; air core linear couplers |
| Purpose | relaying protection and metering |
Request a price and lead time
OBCT internally mounted oil-type bushing current transformer, primary current over 8000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can an old bushing current transformer be replaced without re-setting the protection?
Yes. OBCT units are made with characteristics that match the existing current transformer and to the dimensions of the particular bushing shank.
Which metering accuracy classes are available?
Classes from 0.15S to 2.4 and from 0.2S to 5.0 are offered, and the exact class depends on the ratio selected.
Which winding arrangements can be supplied?
Single ratio (SR), dual ratio (DR) or multi ratio (MR) windings.