LRGBJ-ZH two-stage HV DryShield® current transformer for 220 kV and higher
Instead of one large insulated core, the LRGBJ-ZH stacks two lower-rated sections that share the system voltage equally. Built for extra high voltage substations, it serves both metering and protection.
- Voltage class
- 220 kV and above
- Construction
- cascade (double-decker), two sections
- Insulation
- HV DryShield®
- Duty
- metering and protection
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Primary insulation thickness grows with the square of rated voltage, so a single-core CT at EHV levels needs a great deal of it. The LRGBJ-ZH sidesteps that by splitting the job: each of its two stacked sections handles half the rated voltage, which makes the complete unit much lighter than a one-piece equivalent, and the material saving grows as the voltage class rises. Manufacture is simpler too.
Electrically, the top section's secondary feeds the primary of the bottom section in series. Several secondary windings can be provided on the lower section to suit the user's metering and protection scheme. The top primary sits in series with the network at line potential; its earth screen, secondary winding and housing, together with the lower primary, are bonded at an intermediate potential, while the lower secondary and housing sit at earth.
This double-decker arrangement is normally applied from 220 kV upwards. Documented builds include LRGBJ-ZH-220, LRGBJ-ZH-300, pictured during routine testing, and LRGBJ-ZH-600 for 600 kV.
Because the halves travel as separate pieces, shipping dimensions shrink considerably. On site the crew links the upper secondary to the lower primary, stacks the two parts and bolts them down. The HV DryShield® insulation and its benefits carry over unchanged.
Technical specifications
| Voltage class | 220 kV and above |
|---|---|
| Construction | cascade (double-decker), two sections |
| Insulation | HV DryShield® |
| Duty | metering and protection |
| Section link | upper secondary in series with lower primary |
| Secondary windings | several, on lower section, to user's requirement |
| Versions | LRGBJ-ZH-220, LRGBJ-ZH-300, LRGBJ-ZH-600 (600 kV) |
Request a price and lead time
LRGBJ-ZH two-stage HV DryShield® current transformer for 220 kV and higher. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
From what voltage is the cascade design used?
Generally from 220 kV upwards; the highest listed build, LRGBJ-ZH-600, is rated 600 kV.
How many secondary cores can be fitted?
The lower section can carry several secondary windings, specified by the user for metering and protection.
How is it erected on site?
The two halves arrive separately; the upper secondary is connected to the lower primary, then both parts are stacked and secured.