RIF® FGRBW Tough Dry Transformer Bushing, 40.5–252 kV, 100–3150 A
A fully solid, dry bushing for power transformers in the 40.5–252 kV range, rated 100 to 3150 A. The paper-free RIF® core is free of internal stress and resists pollution and harsh climates.
- Rated voltage
- 40.5–252 kV
- Highest voltage for equipment Um
- 40.5; 72.5; 126; 252 kV
- Rated current Ir
- 100–3150 A
- Rated frequency
- 50 Hz; 60 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Inside the FGRBW Tough there is no oil-impregnated paper at all. The RIF® core is paper-free, completely solid and dry, and is built without internal mechanical stress, which the manufacturer credits for its resistance to pollution and to severe weather. That points the series at substations exposed to heavy pollution or a harsh climate.
Four voltage classes are offered, with highest equipment voltage Um of 40.5, 72.5, 126 and 252 kV, at rated currents from 100 A to 3150 A and 50 Hz or 60 Hz. The single bushing carries the designation FGRB(L)W, and separate versions are made to IEC and to IEEE requirements.
Test levels per class: 95 kV power-frequency withstand for 1 min and 200 kV lightning impulse at 40.5 kV; 140 kV and 325 kV at 72.5 kV; 230 kV and 550 kV at 126 kV; 460 kV and 950 kV at 252 kV. Partial discharge stays at or below 5 pC, and the dissipation factor tanδ is no more than 0.005 at 10 kV and at 1.05 Ur/√3.
Cantilever test loads rise with class and current. A 40.5 kV bushing is tested at 1000 N for 800 A and 1000~1600 A ratings and 2000 N for 2000~2500 A; at 72.5 kV the figures are 1000, 1250 and 2000 N; at 126 kV and 252 kV they are 1250, 1600 and 2500 N.
Service conditions are -50 °C to +45 °C ambient and altitudes up to 1000 m above sea level, with a special design for higher installations. Specific creepage distance is 25 to 31 mm/kV.
Technical specifications
| Rated voltage | 40.5–252 kV |
|---|---|
| Highest voltage for equipment Um | 40.5; 72.5; 126; 252 kV |
| Rated current Ir | 100–3150 A |
| Rated frequency | 50 Hz; 60 Hz |
| Power-frequency withstand, 1 min | 95; 140; 230; 460 kV |
| Lightning impulse withstand | 200; 325; 550; 950 kV peak |
| Partial discharge | ≤ 5 pC |
| Dissipation factor tanδ | ≤ 0.005 at 10 kV and 1.05 Ur/√3 |
| Cantilever test load | 1000–2500 N |
| Insulation | RIF®, paper-free, solid, dry |
| Ambient temperature | -50 to +45 °C |
| Altitude | up to 1000 m |
| Specific creepage distance | 25–31 mm/kV |
Request a price and lead time
RIF® FGRBW Tough Dry Transformer Bushing, 40.5–252 kV, 100–3150 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Is the bushing available to IEC and IEEE?
Yes, the manufacturer builds separate IEC and IEEE versions. Voltage classes are 40.5, 72.5, 126 and 252 kV.
What cantilever load does a 126 kV unit withstand?
1250 N at 800 A, 1600 N at 1000~1600 A and 2500 N at 2000~2500 A. The 252 kV class uses the same values.
Does the insulation contain paper or oil?
No paper is used; the RIF® core is fully solid and dry. Dissipation factor is no more than 0.005 and partial discharge no more than 5 pC.