Cascade_RIF Transformer Bushing for 362 kV and Above, RIF Condenser Core
Cascade_RIF is a power transformer bushing for 362 kV and above, with a condenser core made of RIF resin-impregnated fibreglass. The core is split into graded substructures, each carrying part of the system voltage, and is covered by a silicone outer envelope.
- Voltage class
- 362 kV and above
- Product type
- power transformer bushing
- Core insulation
- multilayer RIF (resin-impregnated fibreglass)
- Core design
- cascade of condenser substructures
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Core insulation in extra-high-voltage bushings becomes very large, which makes manufacture harder and slows delivery. The design tackles this problem by splitting the core into sections arranged end to end. Each section is rated for only a share of the highest system voltage, so the core is no longer one large block.
The core is made of RIF, a multilayer material of fibreglass soaked in resin, and the outer envelope is silicone rubber. Each substructure carries condenser grading, so the voltage along the core is distributed between the sections.
Manufacturers can use production steps already proven on bushings of lower voltage, so the sections are quicker to produce and cost less. Because each section holds less insulation, internal mechanical stresses are easier to control during production. The design relies on established production methods rather than a separate technology for a single large core.
Each section is fitted with a metal tube that carries heat away from the inside of the core and keeps temperature rise down. The manufacturer treats better heat removal, combined with the smaller insulation volume, as the basis for higher long-term stability of the bushing. The bushing is intended for power transformers in extra-high-voltage networks, and the 362 kV Cascade_RIF is the typical example. When selecting one, specify the voltage class, rated current, the transformer it will fit, the connection type to the winding and the mounting flange dimensions.
Technical specifications
| Voltage class | 362 kV and above |
|---|---|
| Product type | power transformer bushing |
| Core insulation | multilayer RIF (resin-impregnated fibreglass) |
| Core design | cascade of condenser substructures |
| Voltage distribution | each substructure takes part of the highest system voltage |
| Outer insulation | silicone rubber |
| Heat dissipation | metal tube in each section |
| Application | extra-high-voltage network transformers |
Request a price and lead time
Cascade_RIF Transformer Bushing for 362 kV and Above, RIF Condenser Core. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which voltage classes do Cascade_RIF bushings cover?
They are rated for 362 kV and above, and the typical design is the 362 kV class.
How does the cascade design differ from a conventional core?
The core is divided into condenser substructures, each carrying a share of the voltage and made with the processes used for lower-voltage bushings.
How is heat removed from the bushing?
Heat is removed through a metal tube in each section, which lowers the temperature rise of the bushing.