TSE / TUSE cast resin dry-type transformers up to 6300 kVA, 35 kV
TSE and TUSE are dry-type transformers with epoxy cast resin insulation rated up to 6300 kVA with HV up to 35 kV. For classes up to 22 kV, 100–6300 kVA are available, and for 35 kV, 100–4000 kVA. The TUSE version is supplied with shielding.
- Power
- 100–6300 kVA (up to 22 kV); 100–4000 kVA (up to 35 kV)
- HV voltage
- up to 35 kV
- LV voltage
- 400/231; 420/242 V
- Regulation
- ±2×2.5 % DETC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The transformers are intended for indoor installation in buildings, substations and industrial facilities. LV voltage is 400/231 or 420/242 V, regulation is ±2×2.5 % DETC. Cooling is AN, and with AN/AF fans the power rises briefly by 40 %. Vector groups are Dyn1, Dyn5 and Dyn11, standards are IEC 60076-11 and EN 50708.
Technical specifications
| Power | 100–6300 kVA (up to 22 kV); 100–4000 kVA (up to 35 kV) |
|---|---|
| HV voltage | up to 35 kV |
| LV voltage | 400/231; 420/242 V |
| Regulation | ±2×2.5 % DETC |
| Cooling | AN; AN/AF (+40 % briefly with fans) |
| Vector groups | Dyn1, Dyn5, Dyn11 |
| Standards | IEC 60076-11, EN 50708 |
Replacement for
ТСЛ-630/10, ТСЛ-1000/10, ТСЗЛ-1600/10, ТСЗГЛ-2500/10; ТСЗ-…/10; dry-type 20–35 kV — ТСЛ/ТСЗЛ (general type); above 4000 kVA and above 35 kV there is no direct serial analog
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
TSE / TUSE cast resin dry-type transformers up to 6300 kVA, 35 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8504 33 00 90 8504 34 00 00 |
|---|---|
| HS, 6 digits | 8504 34 |
| CN (EU) | 8504 33 00 8504 34 00 |
| HTSUS (USA) | 8504 33 00 40 8504 34 00 00 |
| China customs tariff | 8504 33 90 00 8504 34 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What is the maximum power at 35 kV?
For the 35 kV class, 100–4000 kVA are available, and transformers of classes up to 22 kV are built up to 6300 kVA.
How does TUSE differ from TSE?
The TUSE version has shielding, and the insulation in both is epoxy cast resin.
How much can fans increase the power?
In AN/AF mode the power rises briefly by 40 %.
Similar equipment from other manufacturers