ВЛ-108 (VL-108) single-shot auto-reclose time relay, DC 100, 220 V, AC 110, 220, 230 V
The ВЛ-108 (VL-108) switches a single automatic reclosing of lines, busbars and equipment in automation schemes. Operating supply is DC 100, 220 V or AC 110, 220, 230 V, readiness time 30±5 s and start time Tp 0.1 to 50 s.
- Rated supply voltage
- DC 100, 220 V; AC 110, 220, 230 V
- Readiness time
- 30±5 s
- Power consumption
- up to 5 W
- Start time Tp (by version)
- 0.1-10; 0.2-20; 0.5-50 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ВЛ-108 (VL-108) switches one automatic reclosing of lines, busbars or equipment in automation schemes after protection has tripped them, for cases where the fault is not permanent. It works from a DC or AC operating supply and is used in relay protection and emergency automation of power systems.
The supply voltage depends on the version: DC 100, 220 V or AC 110, 220, 230 V. Consumption is up to 5 W. After the supply is applied, the relay becomes ready for operation once the readiness time of 30±5 s has passed.
The start time Tp is set with two switches and depends on the version: 0.1-10 s in steps of 0.1 s, 0.2-20 s in steps of 0.2 s, or 0.5-50 s in steps of 0.5 s. An LED shows the state of the output, and the output contacts are marked 7-8 and 9-10. The manual contains the operating diagram and an example of the command sequence.
The relay is made in version У3 (U3) to GOST 15150. Ambient temperature is -40 to +55 °C at a relative humidity of up to 98 % at 25 °C. Vibration of the mounting points is tolerated at 1-100 Hz with acceleration up to 1g and at 1-15 Hz up to 3g. Conditions of use, installation and servicing are covered by an operating manual shared with the time relays ВЛ100А, ВЛ101А, ВЛ103А, ВЛ104, ВЛ104А and ВЛ108.
Technical specifications
| Rated supply voltage | DC 100, 220 V; AC 110, 220, 230 V |
|---|---|
| Readiness time | 30±5 s |
| Power consumption | up to 5 W |
| Start time Tp (by version) | 0.1-10; 0.2-20; 0.5-50 s |
| Step (by version) | 0.1; 0.2; 0.5 s |
| Output contacts | 7-8, 9-10 |
| Climatic version | У3 (ГОСТ 15150) |
| Ambient temperature | -40...+55 °С |
| Relative humidity | up to 98 % at 25 °С |
| Mounting vibration | 1-100 Hz up to 1g; 1-15 Hz up to 3g |
Part numbers
Show all part numbers (1)
ВЛ-108
How it compares with similar models
| Parameter | ВЛ-108 (VL-108) single-shot auto-reclose time relay, DC 100, 220 V, AC 110, 220, 230 V | ВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply | ВЛ-159М-4 (VL-159M-4) multifunction time relay, 8 functions, pulse counter, 0.1 s - 9999 min | ВЛ-81М (VL-81M) compact three-circuit time relay, 0.1 s - 99 h |
|---|---|---|---|---|
| Rated supply voltage | DC 100, 220 V; AC 110, 220, 230 V | DC 27, 50, 75, 110 V | DC/AC 50, 60 Hz: version 1 - 24-42 V, version 2 - 110-220 V | — |
| Power consumption | up to 5 W | 5 W max. | up to 5 VA (W) | up to 5 VA (W) |
| Output contacts | 7-8, 9-10 | 1з + 1р | 2 changeover | 1 changeover per circuit |
Request a price and lead time
ВЛ-108 (VL-108) single-shot auto-reclose time relay, DC 100, 220 V, AC 110, 220, 230 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the ВЛ-108 used for?
It switches one automatic reclosing of lines, busbars and equipment after a protection trip when the fault is not permanent.
Which operating supply voltages exist?
DC 100, 220 V and AC 110, 220, 230 V.
How is the start time Tp set?
Two switches set it within 0.1-10, 0.2-20 or 0.5-50 s depending on the version, in steps of 0.1, 0.2 or 0.5 s.
Similar equipment from other manufacturers