UKN-01M and UKN-01M2 voltage transformer circuit monitoring relays
The UKN-01M checks the voltage circuits of measuring voltage transformer windings connected in open delta, and the UKN-01M2 checks that those windings are continuous. Input is 100 V, measuring range 0.02–9.0 V, and the supply is = 220 / ~220 V.
- Versions
- UKN-01M (open delta), UKN-01M2 (winding continuity)
- Auxiliary supply voltage
- = 220; ~220 V
- Supply voltage limits
- 90-250 V
- Nominal input signal voltage, 50 Hz
- 100 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The UKN-01M and UKN-01M2 watch the secondary circuits of measuring voltage transformers continuously and automatically. The UKN-01M monitors the integrity of windings connected in open delta, while the UKN-01M2 monitors the continuity of the windings themselves.
Each relay measures the active value of the input signal and extracts its 150 Hz component, and it also measures the 50 Hz component. When the voltage rises above or falls below a setting, the relay operates after the set time delay and records the voltage value at the moment of operation. The input signal value is displayed.
Nominal input signal is 100 V at 50 Hz and the measured voltage range is 0.02–9.0 V. Overvoltage settings run 0.3–9.0 V on the UKN-01M and 0.05–9.0 V on the UKN-01M2, adjustable in 0.01 V steps. Operating time is set between 0.1 and 9.9 s. The reset ratio after the measured voltage falls below the setting is 0.9 – 0.95.
Auxiliary supply is = 220 / ~220 V within limits of 90-250 V. At Uin = 100 V the monitored circuit draws up to 1.0 VA and the supply circuit up to 5.0 VA. Ambient temperature is -20...+55 °C and relative humidity at 25 °C is up to 80 %. Mass is up to 0.7 kg.
Install the relays on panels and control boards of relay rooms, in relay cabinets and in КРУ compartments.
Technical specifications
| Versions | UKN-01M (open delta), UKN-01M2 (winding continuity) |
|---|---|
| Auxiliary supply voltage | = 220; ~220 V |
| Supply voltage limits | 90-250 V |
| Nominal input signal voltage, 50 Hz | 100 V |
| Measured voltage range | 0.02–9.0 V |
| Overvoltage setting range UKN-01M | 0.3–9.0 V |
| Overvoltage setting range UKN-01M2 | 0.05–9.0 V |
| Voltage setting resolution | 0.01 V |
| Operating time setting range | 0.1 - 9.9 s |
| Power drawn by the monitored circuit at Uin = 100 V | max 1.0 VA |
| Power drawn by the supply circuit | max 5.0 VA |
| Reset ratio | 0.9 – 0.95 |
| Ambient temperature | -20...+55 °C |
| Relative humidity at 25 °C | max 80 % |
| Mass | max 0.7 kg |
Part numbers
Show all part numbers (2)
УКН-01М, УКН-01М2
European equivalents
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
UKN-01M and UKN-01M2 voltage transformer circuit monitoring relays. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the UKN-01M and UKN-01M2 differ?
The UKN-01M monitors voltage circuits of transformer windings connected in open delta; the UKN-01M2 monitors continuity of those windings.
What auxiliary supply is needed?
= 220 / ~220 V within 90-250 V, drawing up to 5.0 VA from the supply circuit.
What are the setting ranges?
Voltage 0.3–9.0 V (UKN-01M) or 0.05–9.0 V (UKN-01M2) in 0.01 V steps, and operating time 0.1 - 9.9 s.
Similar equipment from other manufacturers