International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ПЕ46А bistable intermediate relay, 3 changeover and 1 normally open contact

The ПЕ46А is a modular bistable intermediate relay for switching loads in protection, control and automation circuits. Supply is AC/DC 100, 110 or 220 V, outputs are three changeover and one normally open contact, and operate time is not more than 30 ms.

Type
bistable
Supply voltage
AC/DC 100, 110 V or AC/DC 220 V
Permitted supply voltage deviation
± 20%
Pulse current
not more than 40 mA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ПЕ46А two-position relay switches electrical loads in protection, control and automation circuits of power and industrial equipment. It is an electromechanical bistable relay of modular design, rated for switched circuits of 24-250 V DC and AC at 50 Hz.

Contacts change state when voltage is applied to terminals А1-А2 or А3-А2, and the relay stays in its position after the voltage is removed. A pause of not less than 0,3 s is needed between removing voltage from one winding and applying it to the other. The supply comes in two versions, AC/DC 100, 110 V and AC/DC 220 V, with a permitted deviation of ± 20%. Pulse current is not more than 40 mA, and consumption is not more than 1,5 W on DC and 1,5 VA on AC.

The output is three changeover contacts and one normally open contact. Switched voltage is 12-250 V and switched current is from 0,01 to 2 A, with a breaking capacity of not more than 300 VA on AC and 50 W on DC. Operate or reset time is not more than 30 ms, switching endurance is not less than 100000 cycles and the test voltage is 2500 V.

The terminal window is 4 mm2 and takes two wires up to 1,5 mm2. The relay is intended for indoor use in temperate and cold climates, from minus 40 to plus 55 °C and up to 98% relative humidity at 25 °C (У3 version). The site must be protected from precipitation and solar radiation, and the mounting position is arbitrary.

Technical specifications

Typebistable
Supply voltageAC/DC 100, 110 V or AC/DC 220 V
Permitted supply voltage deviation± 20%
Pulse currentnot more than 40 mA
Power consumption, DCnot more than 1,5 W
Power consumption, ACnot more than 1,5 VA
Output contacts3 changeover and 1 normally open
Operate or reset timenot more than 30 ms
Delay between voltage removalnot less than 0,3 s
Switched voltages12-250 V
Switched currentsfrom 0,01 to 2 A
Breaking capacityAC not more than 300 VA; DC not more than 50 W
Switching endurancenot less than 100000 cycles
Test voltage2500 V
Terminal window4 mm2, two wires up to 1,5 mm2
Operating conditionsminus 40 to plus 55 °C, up to 98% at 25 °C, У3 climatic version

How it compares with similar models

ParameterПЕ46А bistable intermediate relay, 3 changeover and 1 normally open contactПЕ45А, ПЕ45А-1 electromagnetic intermediate relay with off-delay of 0,05 - 3,0 sПЕ46, ПЕ46-1 two-position electromagnetic intermediate relay for 24-230 V DC and 24-400 V ACПЕ45Н electromagnetic intermediate relay with off-delay of 0,05 - 1,0 s and neutral relay
Typebistablemonostable, off-delaytwo-position, DC and ACoff-delay, with neutral relay
Switching endurancenot less than 100000 cyclesnot less than 100000 cycles50000 cycles50000 cycles

European equivalents

Auxiliary, bistable and contactor relays for substations

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

ПЕ46А bistable intermediate relay, 3 changeover and 1 normally open contact. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What supply voltages are available for the ПЕ46А?

There are two versions, AC/DC 100, 110 V and AC/DC 220 V, with a permitted deviation of ± 20%.

What happens when the winding voltage is removed?

The relay is bistable and keeps its position. Leave not less than 0,3 s between removing voltage from one winding and applying it to the other.

Which contacts and loads does the ПЕ46А have?

It has three changeover and one normally open contact, switching 12-250 V at 0,01 to 2 A, with a breaking capacity of not more than 300 VA (AC) and 50 W (DC).

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides