Power line carrier teleprotection, 9508 and 9508D terminals with 9512 line tuner, 20–500 kHz
Substation teleprotection and power line carrier equipment built around the 9508 single sideband terminal and its digital 9508D sister. Trip commands, speech and data travel over the HV line itself or into T1/E1 networks.
- RF frequency range
- 20–500 kHz
- Channel bandwidth
- 2.5/4 kHz (9508); 2.5/4/8/16 kHz (9508D)
- Output power
- 50 or 100 W PEP
- Impedance
- 50, 75, 100 or 150 Ohms
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
At the heart of the range is the 9508, an analogue single sideband power line carrier terminal using digital signal processing. Its carrier frequency is set anywhere from 20 kHz to 500 kHz with no parts to swap in the field, the channel bandwidth is 2.5 or 4 kHz and the output is either 50 or 100 W PEP. Plug-in teleprotection modules give up to 8 independent transfer trip commands, every channel supports drop and insert, and the terminal can be tied into an existing or new T1/E1 network.
The 9508D is the digital version, with bandwidths of 2.5/4/8/16 kHz. It carries speech and several data channels of variable rate over a narrow band carrier link and handles drop and insert at T1/E1 level. The 9512 line tuning unit matches the terminal to the line. GARD 8000 and GARD Pro systems complete the range.
Typical duties include direct transfer trip, current differential and phase comparison schemes, anti-islanding and islanding detection, and general substation communications.
Both terminals fit a 19” rack; the 9508 weighs 38 lb. Supplies of 48, 125 or 250 V DC are catered for, with input ranges of 38-60, 88-150 and 200-280 V DC, and line impedance is selectable at 50, 75, 100 or 150 Ohms. The 9508 runs from -20 to +65 °C at 0 to 95% humidity, non-condensing.
The equipment exceeds IEC 60495 and IEC 60834-1. Immunity is proven to ANSI C37.90.1, C37.90.2 and C37.90.3, and dielectric withstand is 2500 V DC to IEC 60255-22-1. Configuration software comes with the equipment.
Technical specifications
| RF frequency range | 20–500 kHz |
|---|---|
| Channel bandwidth | 2.5/4 kHz (9508); 2.5/4/8/16 kHz (9508D) |
| Output power | 50 or 100 W PEP |
| Impedance | 50, 75, 100 or 150 Ohms |
| Nominal supply | 48, 125, 250 V DC |
| Supply range | 38-60, 88-150, 200-280 V DC |
| Trip commands | up to 8 independent |
| Digital interfaces | T1/E1, drop and insert |
| Mounting | 19” rack |
| Weight (9508) | 38 lb |
| Operating temperature (9508) | -20 to +65 °C |
| Humidity | 0 to 95%, non-condensing |
| Standards | IEC 60495, IEC 60834-1, ANSI C37.90.1/.2/.3 |
| Dielectric withstand | 2500 V DC to IEC 60255-22-1 |
Request a price and lead time
Power line carrier teleprotection, 9508 and 9508D terminals with 9512 line tuner, 20–500 kHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What frequency range does the 9508 cover?
The carrier frequency is programmable from 20 kHz to 500 kHz without changing components, with a 2.5 or 4 kHz channel.
How many teleprotection commands can be sent?
With plug-in teleprotection modules the 9508 handles up to 8 independent transfer trip commands.
Can the terminal connect to a digital telecoms network?
Yes, the 9508 and 9508D interconnect with T1/E1 networks and support drop and insert.