EH-d03-160 flameproof transformer assembly for mines, up to 160 kVA, 6000/1200 V

EH-d03-160 is a flameproof transformer assembly for voltages up to 6 kV. It supplies, switches and controls the electric drives of mining machinery, with rated power up to 160 kVA and secondary voltage up to 1200 V, to Directive 2014/34/EU (ATEX).

Rated power
up to 160 kVA
Nominal primary voltage
up to 6000 V
Nominal secondary voltage
up to 1200 V
Total rated current, supply side
up to 28 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The EH-d03-160 transformer assembly supplies, connects and controls the electric drives of machinery and equipment installed in underground workings of non-methane and methane mines. Rated power is up to 160 kVA, nominal primary voltage up to 6000 V and nominal secondary voltage up to 1200 V. Typical loads are conveyors, pumps, loaders and other machines working underground.

The design follows Directive 2014/34/EU (ATEX) and is flameproof. The power protections and the control system, with interlocks to process equipment wired through intrinsically safe circuits, allow the unit to work safely alongside the equipment that feeds the mining machines.

The assembly is prepared for connection to a data transmission system. Process information can be read out and sent to the mine surface, for example to the dispatcher.

Total rated current is up to 28 A on the supply side and up to 180 A on the outgoing side. The 230 V auxiliary outlets are three-phase with a total rated current of 43 A and single-phase up to 20 A. The number of three-phase main outlets and of three-phase and single-phase auxiliary outlets depends on the configuration, and the main and auxiliary circuits are built in several variants.

Control is remote or local. The construction is compact and the unit weighs up to 3150 kg. The circuit set and the number of outlets are fixed by the configuration of each version.

Technical specifications

Rated powerup to 160 kVA
Nominal primary voltageup to 6000 V
Nominal secondary voltageup to 1200 V
Total rated current, supply sideup to 28 A
Total rated current, outgoing sideup to 180 A
230 V three-phase auxiliary outlets, total rated current43 A
230 V single-phase auxiliary outlets, total rated currentup to 20 A
Number of main and auxiliary outletsdepends on configuration
Controlremote / local
Weightup to 3150 kg
DirectiveATEX 2014/34/EU

Request a price and lead time

EH-d03-160 flameproof transformer assembly for mines, up to 160 kVA, 6000/1200 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which workings is the EH-d03-160 intended for?

Underground workings of non-methane and methane mines. The design meets Directive 2014/34/EU (ATEX).

What voltages and currents does the assembly have?

Primary voltage up to 6000 V and secondary up to 1200 V. Total rated current is up to 28 A on the supply side and up to 180 A on the outgoing side.

Can a data transmission system be connected?

Yes. The assembly is prepared for a data transmission system that sends process information to the mine surface, including to the dispatcher.

CIS originals replaced by this item

Similar equipment from other manufacturers