International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PST-b 20/630 underground transformer substation up to 630 kVA

The PST-b 20/630 underground substation is designed for a transformer up to 630 kVA, MV up to 25 kV and LV up to 0.69 kV. The sealed monolithic concrete enclosure is installed under a sidewalk or a square where an above-ground packaged substation cannot be placed.

Transformer rating
up to 630 kVA
MV / LV voltage
up to 25 kV / up to 0.69 kV
LV switchgear current
up to 1250 A
Internal arc withstand
IAC-AB-16 kA-1 s

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The substation is equipped with TPM or Rotoblok SF MV switchgear and RN-W LV switchgear rated up to 1250 A. Internal arc withstand is IAC-AB-16 kA-1 s. The external height of the enclosure is 2800 mm, the internal height is 2050 mm, and the mass is 25 000 kg. This version suits dense urban development and pedestrian zones.

Technical specifications

Transformer ratingup to 630 kVA
MV / LV voltageup to 25 kV / up to 0.69 kV
LV switchgear currentup to 1250 A
Internal arc withstandIAC-AB-16 kA-1 s
External / internal height2800 / 2050 mm
Mass25 000 kg

Request a price and lead time

PST-b 20/630 underground transformer substation up to 630 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 20 91 00
HS, 6 digits8537 20
CN (EU)8537 20 91
HTSUS (USA)8537 20 00 40
China customs tariff8537 20 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What equipment is installed in the PST-b underground substation?

A transformer up to 630 kVA, TPM or Rotoblok SF MV switchgear and RN-W LV switchgear rated up to 1250 A.

What are the dimensions and mass of the substation?

External height 2800 mm, internal height 2050 mm, mass 25 000 kg.

Where is the PST-b underground substation used?

Under sidewalks and squares where an above-ground substation cannot be placed. The enclosure is sealed and monolithic.