TPS201-4 TRUNKSAFE DIN Carrier, fault-tolerant fieldbus power for 4 segments
The TPS201-4 is the DIN carrier of the TRUNKSAFE fault-tolerant system, supplying redundant DC power to up to four FOUNDATION fieldbus H1 or PROFIBUS PA segments. Communication with field devices continues after any single point failure, such as an open single wire.
- Model
- TPS201-4
- Type
- DIN carrier of a fault-tolerant fieldbus power supply (TRUNKSAFE)
- Networks
- FOUNDATION fieldbus H1, PROFIBUS PA
- Number of segments
- up to 4
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TPS201-4 is the DIN carrier of the TRUNKSAFE Fault-Tolerant Fieldbus System, supplying redundant DC power to fieldbus segments. One carrier serves up to four FOUNDATION fieldbus H1 or PROFIBUS PA segments. The system keeps communications running between field devices and the host after any single point failure on a segment, such as an open single wire.
For physical-layer redundancy TRUNKSAFE uses two trunk cables (legs A and B). In normal operation the segment is terminated at each end by the redundant power conditioners. When an open or short circuit is detected, the TRUNKSAFE device coupler starts automatic termination of the healthy leg, so communications continue across the whole segment. The host is told of the fault by a contact closure output. The system complies with FF831-1 and FF846-1 and with the IEC 61158-2 physical layer standard, and no change to field devices or DCS-level software is needed.
The carrier accepts 19.2-32 Vdc and delivers up to 350 mA per segment, with 500 Vdc DC/DC isolation. LED diagnostics show open circuits, short circuits and noise. The system can include the TPS202 Advanced Power Conditioner, the FDM252 diagnostics module, the SPM201 surge protection module and TS200 series device couplers. Host interface kits are available for Yokogawa, DeltaV and PROFIBUS PA hosts.
It mounts on 32 mm or 35 mm rail. For outdoor or hazardous locations an external enclosure of at least IP54 is required. Dimensions are 216 x 114 x 121 mm. The FM certification is Non-Incendive Class I, Division 2, Groups A, B, C, D, T4A Ta=70°C. ATEX is II 3 G Ex nA nC [ic] IIC T4, Ta -40 to +70 °C, and IECEx is Ex nA nC [nL] IIC T4. The unit carries CE, meets EN 61326 and is RoHS compliant.
Technical specifications
| Model | TPS201-4 |
|---|---|
| Type | DIN carrier of a fault-tolerant fieldbus power supply (TRUNKSAFE) |
| Networks | FOUNDATION fieldbus H1, PROFIBUS PA |
| Number of segments | up to 4 |
| Redundancy | Redundant Trunk, two trunk cables (A and B) |
| Input | 24 Vdc, range 19.2-32 Vdc |
| Output | Redundant DC segment power, up to 350 mA per segment |
| Isolation | DC/DC 500 Vdc |
| Diagnostics | LEDs: open circuit, short circuit, noise |
| Modules | TPS202, FDM252, SPM201, TS200 couplers |
| Mounting | 32 mm or 35 mm rail; external enclosure of IP54 minimum for outdoor use |
| Dimensions | 216 x 114 x 121 mm |
| Certification | FM Non-Incendive Class I, Div. 2, Groups A, B, C, D, T4A; ATEX II 3 G Ex nA nC [ic] IIC T4; IECEx Ex nA nC [nL] IIC T4 |
| RoHS | Yes |
Part numbers
Show all part numbers (1)
TPS201-4
How it compares with similar models
| Parameter | TPS201-4 TRUNKSAFE DIN Carrier, fault-tolerant fieldbus power for 4 segments | TG208-DIN 8-Spur Fieldbus Device Coupler for FOUNDATION fieldbus H1 and PROFIBUS PA | TPS400 TRUNKGUARD Simplex Fieldbus Power Supply for 4 H1 segments | HMC HART-to-MODBUS Converter, 24 VDC, DIN-rail mount |
|---|---|---|---|---|
| Type | DIN carrier of a fault-tolerant fieldbus power supply (TRUNKSAFE) | Fieldbus device coupler, 8 spurs, no enclosure | Simplex fieldbus power supply on a DIN carrier | HART-to-MODBUS converter |
| Input | 24 Vdc, range 19.2-32 Vdc | — | 24 Vdc (inputs A and B), range 19.2-32 Vdc | HART (from TCM only) |
| Output | Redundant DC segment power, up to 350 mA per segment | — | Redundant-capable DC segment power, 350 mA (TPS202) or 500 mA (TPS205) per segment | MODBUS RTU |
| Certification | FM Non-Incendive Class I, Div. 2, Groups A, B, C, D, T4A; ATEX II 3 G Ex nA nC [ic] IIC T4; IECEx Ex nA nC [nL] IIC T4 | Non-Incendive/Div. 2, Zone 2, General Purpose; ATEX II 3 G Ex nA [ic] IIC T5; IECEx Ex nA [nL] IIC T5 | FOUNDATION Fieldbus Registered, FF831-1; non-incendive use with a Non-Incendive/Div. 2, Zone 2, General Purpose coupler | — |
Request a price and lead time
TPS201-4 TRUNKSAFE DIN Carrier, fault-tolerant fieldbus power for 4 segments. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is preserved if a trunk wire breaks?
Communication with the field devices: the system uses two trunk cables, and the healthy leg is terminated automatically.
What supply and current does the carrier give?
An input of 19.2-32 Vdc and up to 350 mA per segment.
Which networks is the TPS201-4 for?
FOUNDATION fieldbus H1 and PROFIBUS PA segments, up to four segments per carrier.
Similar equipment from other manufacturers