TG208-DIN 8-Spur Fieldbus Device Coupler for FOUNDATION fieldbus H1 and PROFIBUS PA
The TG208-DIN is an 8-spur device coupler of the TG200 TRUNKGUARD series for DIN rail. It connects several field devices to a main fieldbus trunk in FOUNDATION fieldbus H1 and PROFIBUS PA networks. Its spur short-circuit protection resets automatically.
- Model
- TG208-DIN
- Type
- Fieldbus device coupler, 8 spurs, no enclosure
- Networks
- FOUNDATION fieldbus H1, PROFIBUS PA
- Power
- Bus powered, 10-32 Vdc
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TG208-DIN is an 8-spur device coupler of the TG200 TRUNKGUARD series, supplied as a DIN-rail unit without enclosure. It connects multiple devices to a main fieldbus trunk in FOUNDATION fieldbus H1 and PROFIBUS PA networks. The TG200 series includes models that handle four to 20 devices. The coupler is bus powered from 10 to 32 Vdc, with a maximum segment current of 1.5 A.
Spur protection is electronic and fully auto-resetting. With the Fold-Back technique, any spur that tries to draw more than 48 mA is switched off and receives no current until the fault is removed. During a short circuit the spur draws only 4-5 mA. When the short is cleared the spur reconnects to the segment automatically, so one device fault does not bring the segment down.
The Automatic Segment Termination feature removes segment failure caused by under or over termination, and keeps local parts of a segment working if remote parts are accidentally disconnected. Where external termination is preferred, the -MT option (TG208-DIN-MT) is supplied without the auto-terminator.
Diagnostics are by LED: spur status is green for normal and red for a short, and the auto-terminator LED is yellow when auto-termination is active. A front-panel connection serves a fieldbus hand-held communicator. Spur wiring can run up to 120 m. Removable screw-clamp terminals take wire of 0.8-2.5 mm2 (12-24 AWG). The spur voltage drop is 0.4 V at 20 mA and the trunk IN to OUT drop is 0.7 V. Quiescent current of the TG208 is 18 mA at 32 V and 9 mA at 16 V. The temperature range is -40 to +70 °C and the size is 152 x 50 x 82 mm.
The series is intended for general purpose and Non-Incendive/Div. 2, Zone 2 locations. The FM certification is Non-Incendive Class I, Division 2, Groups A, B, C, D, T5 Ta=70°C. ATEX is II 3 G Ex nA [ic] IIC T5, Ta -40 to +70 °C, and IECEx is Ex nA [nL] IIC T5. The unit is RoHS compliant and meets EN 61326.
Technical specifications
| Model | TG208-DIN |
|---|---|
| Type | Fieldbus device coupler, 8 spurs, no enclosure |
| Networks | FOUNDATION fieldbus H1, PROFIBUS PA |
| Power | Bus powered, 10-32 Vdc |
| Maximum segment current | 1.5 A |
| Spur protection | Fold-Back, switch-off above 48 mA, auto-resetting |
| Spur short-circuit load | 4-5 mA |
| Auto-terminator | Automatic Segment Termination (absent with -MT option) |
| Indicators | Spur: green/red; auto-terminator: yellow |
| Spur length | up to 120 m |
| Terminals | Removable screw-clamp, 0.8-2.5 mm2 (12-24 AWG) |
| Voltage drop | Spur 0.4 V at 20 mA; trunk IN to OUT 0.7 V |
| Quiescent current | 18 mA at 32 V; 9 mA at 16 V |
| Temperature range | -40 to +70 °C |
| Dimensions | 152 x 50 x 82 mm |
| Certification | Non-Incendive/Div. 2, Zone 2, General Purpose; ATEX II 3 G Ex nA [ic] IIC T5; IECEx Ex nA [nL] IIC T5 |
| RoHS | Yes |
Part numbers
Show all part numbers (2)
TG208-DIN, TG208-DIN-MT
How it compares with similar models
| Parameter | TG208-DIN 8-Spur Fieldbus Device Coupler for FOUNDATION fieldbus H1 and PROFIBUS PA | TPS201-4 TRUNKSAFE DIN Carrier, fault-tolerant fieldbus power for 4 segments | TG300 TRUNKGUARD fieldbus device coupler for Zone 1, TG308-DIN with 8 spurs | TS200 TRUNKSAFE fault-tolerant fieldbus device coupler, 12 spurs |
|---|---|---|---|---|
| Type | Fieldbus device coupler, 8 spurs, no enclosure | DIN carrier of a fault-tolerant fieldbus power supply (TRUNKSAFE) | Fieldbus device coupler | Fault-tolerant fieldbus device coupler |
| Power | Bus powered, 10-32 Vdc | — | Bus powered, 10 to 32 V DC | Bus powered |
Request a price and lead time
TG208-DIN 8-Spur Fieldbus Device Coupler for FOUNDATION fieldbus H1 and PROFIBUS PA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many devices does the TG208-DIN connect?
Up to 8 field devices on spurs to the main fieldbus trunk.
How is a segment protected from a short circuit on a spur?
By the Fold-Back technique: a spur drawing more than 48 mA is switched off and reconnects automatically once the short is cleared.
What supply is needed, and is termination automatic?
It is bus powered from 10-32 Vdc. Automatic Segment Termination is built in, except with the -MT option, which omits the auto-terminator.
Similar equipment from other manufacturers