532 1/4 DIN Auto/Manual Station, manual backup for control loops
The 532 is a 1/4 DIN panel station that provides manual backup for critical control loops. In HOST mode the control signal from the host device passes through it without degradation. Version 532-12110B0000 has one universal input, one 4-20 mA output, three 5 A relays and a 90-250 Vac supply.
- Model
- 532-12110B0000
- Function
- Auto/Manual backup station
- Input
- 1 programmable universal PV input and CV from the primary control loop
- Analogue output
- 1 x 4-20 mA output (CV)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 532 is a 1/4 DIN Auto/Manual station that backs up critical control loops by hand. In HOST mode the control signal from the host device, which may be a PLC, a DCS or a process controller, passes through the station without degradation. It switches to LOCAL mode on keypad selection, a digital input or loss of the host signal. In LOCAL mode it generates the control signal from a predetermined control value (CV) or from the last known CV from the host, and the operator adjusts the CV with the keys. It returns to HOST mode on keypad selection, opening of the digital input or return of the host signal. Removing the station from its case, or powering it down while in HOST mode, does not disturb the host signal.
Version 532-12110B0000 carries one programmable universal PV input with the CV from the primary control loop, one 4-20 mA analogue output for the CV and three mechanical relays rated 5 A. The input accepts a retransmitted PV, or thermocouples, RTDs and linear signals directly. The supply is universal AC, 90-250 Vac. Inputs and outputs are isolated.
The front face meets NEMA 4X for watertight operation, so the unit can be hosed down with the surrounding equipment. The housing is solid metal with illuminated rubber keys. The vacuum fluorescent display has one large five-digit field and two lines of nine alphanumeric characters each. Alarm messages can be programmed by the user. The display always shows the CV and can also show the PV and setpoint (SP) or valve position (VP).
The station fits a standard 1/4 DIN panel cutout. Overall length is 182.37 mm, front width 95.76 mm and depth 152.40 mm, and the cutout width runs from 92.00 to 92.80 mm. Mounting hardware is included, and the instrument enclosure mounting must be earthed. The unit is UL approved.
Technical specifications
| Model | 532-12110B0000 |
|---|---|
| Function | Auto/Manual backup station |
| Input | 1 programmable universal PV input and CV from the primary control loop |
| Analogue output | 1 x 4-20 mA output (CV) |
| Relay outputs | 3 mechanical relays, 5 A |
| Power | Universal AC, 90-250 V |
| Modes | HOST, LOCAL |
| Housing | 1/4 DIN panel mount, NEMA 4X front |
| Display | Vacuum fluorescent, five-digit field and two lines of 9 characters |
| Overall length | 182.37 mm |
| Front width | 95.76 mm |
| Depth | 152.40 mm |
| Panel cutout width | 92.00-92.80 mm |
| Options | RS-485, three digital inputs, 24 V AC/DC operation, CE, triac relay 1 A, DC logic, loop power |
| Approvals | UL, RoHS |
Part numbers
Show all part numbers (1)
532-12110B0000
How it compares with similar models
| Parameter | 532 1/4 DIN Auto/Manual Station, manual backup for control loops | 545 1/4 DIN Dual Loop Process Controller, 2 universal inputs, 2 x 4-20 mA outputs | 555 1/4 DIN Chlorination/Dechlorination Controller, 2 inputs, 2 x 4-20 mA | 535-PROFILE 1/4 DIN Process Controller with profile and recipe control |
|---|---|---|---|---|
| Function | Auto/Manual backup station | Dual-loop PID controller, cascade, ratio, feed forward | Chlorination and dechlorination controller | Single loop controller, profile or recipe control |
| Relay outputs | 3 mechanical relays, 5 A | 2 mechanical relays, 5 A | 2 mechanical relays, 5 A | — |
| Housing | 1/4 DIN panel mount, NEMA 4X front | 1/4 DIN panel mount, NEMA 4X front | 1/4 DIN panel mount, NEMA 4X front | 1/4 DIN panel mount, NEMA 4X |
| Display | Vacuum fluorescent, five-digit field and two lines of 9 characters | Vacuum fluorescent, 3 lines | Vacuum fluorescent, five-digit readout and 2 lines of 9 characters | — |
| Options | RS-485, three digital inputs, 24 V AC/DC operation, CE, triac relay 1 A, DC logic, loop power | Remote setpoint, 5 digital inputs, slidewire, RS-485, 24 V AC/DC | — | Remote setpoint and profile, 5 digital inputs and CE, RS-485 |
Request a price and lead time
532 1/4 DIN Auto/Manual Station, manual backup for control loops. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
When does the 532 switch to LOCAL mode?
On keypad selection, a digital input or loss of the host signal. It then generates the CV from a preset or the last known value.
Does removing the station disturb the loop signal?
No. Removing it from its case, or powering down in HOST mode, does not disturb the host signal.
Which outputs does version 532-12110B0000 have?
One 4-20 mA analogue output for the CV and three mechanical relays rated 5 A.