PSSP Silicone Station Post Insulators, Series 175 and 250, BIL 110–900 kV
Station posts with a water-repellent silicone housing that carry busbars, disconnectors and other substation apparatus from 15 kV up to 230 kV. Ten sizes match technical reference numbers TR205 to TR304, so a porcelain post can be exchanged like for like.
- Series
- 175, 250
- Housing material
- silicone
- Nominal system voltage
- 15–69 kV (175); 69–230 kV (250)
- BIL
- 110–350 kV (175); 350–900 kV (250)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Two series cover the voltage range. Series 175 serves nominal system voltages of 15, 25, 35, 46 and 69 kV, with BIL ratings from 110 to 350 kV, heights between 254 mm and 762 mm and leakage distances of 450–2200 mm. Series 250 starts at 69 kV and goes up to 230 kV, with BIL from 350 to 900 kV, heights of 762–2032 mm and leakage distances of 1550–5800 mm.
On the smaller series the maximum design cantilever load drops from 16.5 kN on PSSP175TR205 to 4.4 kN on PSSP175TR216, while the specified tensile and compression loads stay at 89 kN for all five sizes. Wet withstand at 60 Hz rises from 40 to 155 kV on series 175 and from 150 to 395 kV on series 250. Positive critical impulse flashover sits between 125 and 390 kV on the 175 range and reaches 1010 kV on PSSP250TR304.
Inside, a core is enclosed in silicone moulded directly over it, which keeps moisture out of the interior. The sheds alternate in diameter, 150 mm and 119 mm on series 175, and the silicone surface sheds water, helping on polluted sites. End fittings are galvanised steel, tapped on a 76 mm (3 in) bolt circle for series 175 and on a 5 in bolt circle for series 250, identical at the top and the base.
Weights on series 175 run from 3.91 kg to 6.94 kg, noticeably lighter than porcelain, and the housing stands up better to vandalism. For each TR number the manufacturer also lists a porcelain equivalent, so a bay can be converted one post at a time without changing the steelwork.
Technical specifications
| Series | 175, 250 |
|---|---|
| Housing material | silicone |
| Nominal system voltage | 15–69 kV (175); 69–230 kV (250) |
| BIL | 110–350 kV (175); 350–900 kV (250) |
| Height | 254–762 mm (175); 762–2032 mm (250) |
| Leakage distance | 450–2200 mm (175); 1550–5800 mm (250) |
| Wet withstand 60 Hz | 40–155 kV (175); 150–395 kV (250) |
| Max design cantilever load | 16.5–4.4 kN (175) |
| Specified tensile and compression load | 89 kN (175) |
| End fittings | galvanised steel |
| Bolt circle | 76 mm (175); 5 in (250) |
| Sheds | alternating large and small |
| Technical reference numbers | TR205–TR216 (175); TR278–TR304 (250) |
Request a price and lead time
PSSP Silicone Station Post Insulators, Series 175 and 250, BIL 110–900 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which size suits a 69 kV system?
Either PSSP175TR216 at 762 mm high or PSSP250TR278 with a 1550 mm leakage distance; both carry a BIL of 350 kV.
Will it bolt straight onto an existing porcelain post position?
Each size follows a TR reference number and uses tapped fittings on a 76 mm bolt circle for series 175 or a 5 in bolt circle for series 250, matching the porcelain equivalent.
How much leakage distance do the tallest posts offer?
Series 250 goes from 1550 mm on PSSP250TR278 to 5800 mm on PSSP250TR304, which together with the silicone housing suits heavily polluted sites.