SQRVEx .2 explosion-proof variable-speed actuators for modulating duty
SQRVEx .2 is a part-turn actuator with variable operating time, certified for potentially explosive atmospheres and rated for modulating duty. Torque is 150 Nm to 2400 Nm, modulating torque 75 Nm to 1200 Nm, up to 1500 c/h.
- Type
- Explosion-proof variable-speed actuator for modulating duty
- Duty
- modulating (class C) S4 - 25 %
- Torque range
- 150 Nm - 2400 Nm
- Modulating torque range
- 75 Nm - 1200 Nm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The SQRVEx .2 gives electric actuation with a variable operating time in areas that carry an explosion risk. It is certified for use in potentially explosive atmospheres and designed for modulating duty, class C, S4 - 25 %.
The ATEX marking reads II 2G Ex db eb IIC (IIB) T4 (T3) II 2G Ex db IIC (IIB) T4 (T3). The IECEx marking is Ex db eb IIC (IIB) T4 (T3) Ex db IIC (IIB) T4 (T3). The FM entries are FM CLASS I DIV 1 GROUPS (B), C, D T4 (T3C), FM CLASS II DIV 1 GROUPS E, F, G T4 (T3C) and FM CLASS III DIV 1 T4 (T3).
Torque is 150 Nm to 2400 Nm, modulating torque 75 Nm to 1200 Nm, with a maximum of 1500 starts per hour. A 90° stroke takes 4 s to 360 s within swing angles of 75 ° to 105 °. The enclosure is IP68, corrosion protection is class KS, and the ambient temperature range is -30 °C to +40/+60 °C.
The mains connection is 1-phase or 3-phase. The actuator senses limit positions and torque, and has a handwheel and a mechanical position indicator. Intermediate position switches, switches in tandem version, a position transmitter and a magnetic limit and torque transmitter are options.
Functions include programmable potential-free output contacts, soft start and stop, an operating time profile against pressure surges, separate operating times for EMERGENCY and safety behaviour, a process controller (PID), fieldbus control and operation data logging. Behaviour on emergencies and communication loss is programmable, and a Bluetooth interface links a notebook or Android tablet. Connection is by plug/socket connector or cable entries; valve attachments follow DIN and ISO standards.
Technical specifications
| Type | Explosion-proof variable-speed actuator for modulating duty |
|---|---|
| Duty | modulating (class C) S4 - 25 % |
| Torque range | 150 Nm - 2400 Nm |
| Modulating torque range | 75 Nm - 1200 Nm |
| Number of starts (max.) | 1500 c/h |
| Operating time for 90° | 4 s - 360 s |
| Swing angles | 75 ° - 105 ° |
| Enclosure protection | IP68 |
| Corrosion protection | KS |
| Ambient temperature | -30 °C - +40/+60 °C |
| Mains connection | 1-phase and 3-phase |
| Functions | programmable potential-free output contacts, soft start and stop, operating time profile, process controller (PID), fieldbus control, data logging, Bluetooth |
| ATEX marking | II 2G Ex db eb IIC (IIB) T4 (T3) II 2G Ex db IIC (IIB) T4 (T3) |
| FM marking | FM CLASS I DIV 1 GROUPS (B), C, D T4 (T3C) FM CLASS II DIV 1 GROUPS E, F, G T4 (T3C) FM CLASS III DIV 1 T4 (T3) |
| IECEx marking | Ex db eb IIC (IIB) T4 (T3) Ex db IIC (IIB) T4 (T3) |
How it compares with similar models
| Parameter | SQRVEx .2 explosion-proof variable-speed actuators for modulating duty | SQVEx .2 explosion-proof variable-speed actuators for open-close duty, 150–2400 Nm | SQREx .2 explosion-proof part-turn actuators for modulating duty, 50–2400 Nm | SQRV .2 variable-speed part-turn actuators for modulating duty |
|---|---|---|---|---|
| Type | Explosion-proof variable-speed actuator for modulating duty | Explosion-proof variable-speed part-turn actuator | Explosion-proof part-turn actuator for modulating duty | Variable-speed part-turn actuator for modulating duty |
| Duty | modulating (class C) S4 - 25 % | open-close and positioning (classes A and B), S2 - 15 min | modulating | modulating (class C) S4 - 25 % |
| Torque range | 150 Nm - 2400 Nm | 150 Nm - 2400 Nm | 50 Nm - 2400 Nm | 150 Nm - 2400 Nm |
| Modulating torque range | 75 Nm - 1200 Nm | — | 75 Nm - 1200 Nm | 52 Nm - 840 Nm |
| Operating time for 90° | 4 s - 360 s | 4 s - 360 s | 8 s - 100 s | 4 s - 360 s |
| Ambient temperature | -30 °C - +40/+60 °C | -30 °C - +40/+60 °C | -30 °C - +40/+60 °C | -30 °C - +70 °C |
Request a price and lead time
SQRVEx .2 explosion-proof variable-speed actuators for modulating duty. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What Ex marking does the SQRVEx .2 carry?
ATEX: II 2G Ex db eb IIC (IIB) T4 (T3) and II 2G Ex db IIC (IIB) T4 (T3). IECEx: Ex db eb IIC (IIB) T4 (T3) and Ex db IIC (IIB) T4 (T3).
What is the operating time for 90°?
4 s to 360 s.
Does the actuator support fieldbus control?
Yes. Fieldbus control, a process controller (PID) and operation data logging are among its functions.
Similar equipment from other manufacturers