SQRV .2 variable-speed part-turn actuators for modulating duty
SQRV .2 adds variable operating times to the part-turn range for modulating duty, together with ACV 01.2 actuator controls. Torque is 150 Nm to 2400 Nm, modulating torque 52 Nm to 840 Nm, and a 90° stroke takes 4 s to 360 s.
- Type
- Variable-speed part-turn actuator for modulating duty
- Duty
- modulating (class C) S4 - 25 %
- Torque range
- 150 Nm - 2400 Nm
- Modulating torque range
- 52 Nm - 840 Nm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The SQRV .2 extends the SQ/SQR part-turn range with models whose operating time can be varied. Paired with ACV 01.2 actuator controls, it covers a range of operating times with a ratio of up to 1:10. It is designed for modulating duty, class C, S4 - 25 %.
Output torque is 150 Nm to 2400 Nm, and the modulating torque range is 52 Nm to 840 Nm. A 90° stroke takes 4 s to 360 s, within swing angles of 75 ° to 105 °. The enclosure is IP68, corrosion protection is class KS, and the ambient temperature range is -30 °C to +70 °C.
The mains connection is 1-phase or 3-phase. The actuator senses limit positions and torque and has a handwheel and a mechanical position indicator. Intermediate position switches, switches in tandem version, a position transmitter and a magnetic limit and torque transmitter are available. In selected configurations, safe end position feedback up to SIL 2 is possible.
On the functional side it offers programmable potential-free output contacts for status signalling, soft start and stop for gentle valve operation, and an operating time profile that avoids pressure surges. Separate operating times can be set for EMERGENCY and safety behaviour. Further functions are a process controller (PID), fieldbus control, programmable behaviour on emergencies and communication loss, and operation data logging. A Bluetooth interface connects a notebook or an Android tablet.
Connection is through the manufacturer's plug/socket connector, with terminals as an option, or cable entries; valve attachments follow DIN and ISO standards.
Technical specifications
| Type | Variable-speed part-turn actuator for modulating duty |
|---|---|
| Duty | modulating (class C) S4 - 25 % |
| Torque range | 150 Nm - 2400 Nm |
| Modulating torque range | 52 Nm - 840 Nm |
| Operating time for 90° | 4 s - 360 s |
| Swing angles | 75 ° - 105 ° |
| Enclosure protection | IP68 |
| Corrosion protection | KS |
| Ambient temperature | -30 °C - +70 °C |
| Mains connection | 1-phase and 3-phase |
| Functions | programmable potential-free output contacts, soft start and stop, operating time profile, process controller (PID), fieldbus control, data logging, Bluetooth |
| Actuator controls | ACV 01.2 |
How it compares with similar models
| Parameter | SQRV .2 variable-speed part-turn actuators for modulating duty | SQV .2 variable-speed part-turn actuators for open-close duty, 150–2400 Nm | SQRVEx .2 explosion-proof variable-speed actuators for modulating duty | SQR .2 part-turn actuators for modulating duty, 50–2500 Nm |
|---|---|---|---|---|
| Type | Variable-speed part-turn actuator for modulating duty | Variable-speed part-turn actuator | Explosion-proof variable-speed actuator for modulating duty | Part-turn actuator for modulating duty |
| Duty | modulating (class C) S4 - 25 % | open-close and positioning (classes A and B), S2 - 15 min | modulating (class C) S4 - 25 % | modulating (class C) S4 - 25 % |
| Torque range | 150 Nm - 2400 Nm | 150 Nm - 2400 Nm | 150 Nm - 2400 Nm | 50 Nm - 2500 Nm |
| Modulating torque range | 52 Nm - 840 Nm | — | 75 Nm - 1200 Nm | 75 Nm - 1200 Nm |
| Operating time for 90° | 4 s - 360 s | 4 s - 360 s | 4 s - 360 s | 8 s - 100 s |
| Ambient temperature | -30 °C - +70 °C | -30 °C - +70 °C | -30 °C - +40/+60 °C | -30 °C - +70 °C |
Request a price and lead time
SQRV .2 variable-speed part-turn actuators for modulating duty. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What operating time range does the SQRV .2 cover?
4 s to 360 s for 90°, with an operating time ratio of up to 1:10.
Which controls go with the SQRV .2?
ACV 01.2 actuator controls.
Is safe end position feedback available?
Yes, in selected configurations safe end position feedback up to SIL 2 is possible.