SQR .2 part-turn actuators for modulating duty, 50–2500 Nm
The SQR .2 range is the modulating version of the part-turn actuator, rated for class C duty S4 - 25 %. Torque is 50 Nm to 2500 Nm, modulating torque 75 Nm to 1200 Nm, with up to 1500 starts per hour and 8 s to 100 s for 90°.
- Type
- Part-turn actuator for modulating duty
- Duty
- modulating (class C) S4 - 25 %
- Torque range
- 50 Nm - 2500 Nm
- Modulating torque range
- 75 Nm - 1200 Nm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
SQR .2 actuators are the part-turn type for regulating valves. They are designed for modulating duty, class C, S4 - 25 %. Output torque is 50 Nm to 2500 Nm, of which 75 Nm to 1200 Nm applies to modulating operation, and the maximum number of starts is 1500 c/h.
A 90° stroke takes 8 s to 100 s, and swing angles run from 75 ° to 105 °. The enclosure is IP68, corrosion protection is class KS, and the ambient temperature range is -30 °C to +70 °C.
As with the other actuators of this family, the controls can be chosen freely: a simple OPEN-CLOSE unit, or a micro-controlled version that logs operating data or has a fieldbus interface.
Each actuator senses limit positions and torque, runs on a 3-phase or 1-phase AC motor, and carries a handwheel and a mechanical position indicator. Intermediate position switches, switches in tandem version, a position transmitter and a magnetic limit and torque transmitter can be added.
Selected configurations reach SIL 2, and SIL 3 is possible with AC 01.2 SIL actuator controls. Electrical connection is through the manufacturer's plug/socket connector, with terminals as an option, or through cable entries; valve attachments follow DIN and ISO standards.
Technical specifications
| Type | Part-turn actuator for modulating duty |
|---|---|
| Duty | modulating (class C) S4 - 25 % |
| Torque range | 50 Nm - 2500 Nm |
| Modulating torque range | 75 Nm - 1200 Nm |
| Number of starts (max.) | 1500 c/h |
| Operating time for 90° | 8 s - 100 s |
| Swing angles | 75 ° - 105 ° |
| Enclosure protection | IP68 |
| Corrosion protection | KS |
| Ambient temperature | -30 °C - +70 °C |
| Functional safety | up to SIL 2 in selected configurations; up to SIL 3 with AC 01.2 SIL |
How it compares with similar models
| Parameter | SQR .2 part-turn actuators for modulating duty, 50–2500 Nm | SQ .2 part-turn actuators for open-close duty, 50–2500 Nm | SQREx .2 explosion-proof part-turn actuators for modulating duty, 50–2400 Nm | SQRV .2 variable-speed part-turn actuators for modulating duty |
|---|---|---|---|---|
| Type | Part-turn actuator for modulating duty | Part-turn actuator | Explosion-proof part-turn actuator for modulating duty | Variable-speed part-turn actuator for modulating duty |
| Duty | modulating (class C) S4 - 25 % | open-close and positioning (classes A and B), S2 - 15 min | modulating | modulating (class C) S4 - 25 % |
| Torque range | 50 Nm - 2500 Nm | 50 Nm - 2500 Nm | 50 Nm - 2400 Nm | 150 Nm - 2400 Nm |
| Modulating torque range | 75 Nm - 1200 Nm | — | 75 Nm - 1200 Nm | 52 Nm - 840 Nm |
| Operating time for 90° | 8 s - 100 s | 4 s - 100 s | 8 s - 100 s | 4 s - 360 s |
| Ambient temperature | -30 °C - +70 °C | -30 °C - +70 °C | -30 °C - +40/+60 °C | -30 °C - +70 °C |
Request a price and lead time
SQR .2 part-turn actuators for modulating duty, 50–2500 Nm. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many starts per hour does the SQR .2 allow?
Up to 1500 c/h.
Which duty class applies?
Modulating duty, class C, S4 - 25 %, with a modulating torque of 75 Nm to 1200 Nm.
Which controls can be combined with the SQR .2?
Anything from a simple OPEN-CLOSE unit to a micro-controlled version with operating data logging or a fieldbus interface.