A cabinet, motor or luminaire nameplate usually carries two or three codes: IP66, IK08 and, on North American equipment, NEMA 4X as well. Each answers a different question. IP covers dust and water, IK covers impacts, and NEMA covers the environment as a whole, including corrosion and icing. That is why one code cannot simply be swapped for another.

The IP code: two digits and optional letters

IP 6 6 D H │ │ │ │ └ supplementary letter for the equipment (H, M, S, W) │ │ │ └ additional letter for protection of persons (A–D) │ │ └ second digit: water (0–9) │ └ first digit: solid objects and dust (0–6) └ International Protection

The code is defined by IEC 60529. CIS countries use the identical GOST 14254-2015; Ukraine uses DSTU EN 60529. When a characteristic is not rated, an X takes its place: IPX4 means only splashing water was tested and no dust protection is claimed.

First digit: solid objects
DigitProtection
0none
1objects over 50 mm (back of the hand)
2over 12.5 mm (finger)
3over 2.5 mm (tool)
4over 1.0 mm (wire)
5dust-protected: some dust enters but does not interfere with operation
6dust-tight
Second digit: water
DigitTest
0no protection
1vertically dripping water
2dripping water with the enclosure tilted up to 15°
3spraying water up to 60° from vertical
4splashing water from any direction
5water jets (6.3 mm nozzle, 12.5 L/min)
6powerful jets (12.5 mm nozzle, 100 L/min)
7temporary immersion up to 1 m for 30 min
8continuous immersion under conditions harder than 7, stated by the manufacturer
9high-pressure, high-temperature jets (washdown)

Digits 7 and 8 do not include 5 and 6. An enclosure that survives immersion can still leak under a jet, because the pressure acts differently. Outdoor equipment is therefore often dual-rated: IP66/IP67. The additional letters A–D show protection of persons against access to hazardous parts when it is higher than the first digit implies. The letters H, M, S and W describe the equipment itself: H for high-voltage apparatus, M and S for water tests with the equipment moving or stationary, W for specified weather conditions.

The IK code: impact energy

IEC 62262 rates enclosure resistance to external mechanical impacts for equipment up to 72.5 kV. The code always has two digits, from IK00 to IK10; a 2021 amendment added IK11. Behind each code is the impact energy in joules that the enclosure withstands without losing its protective properties.

IK classes
CodeImpact energy
IK00not rated
IK010.14 J
IK020.2 J
IK030.35 J
IK040.5 J
IK050.7 J
IK061 J
IK072 J
IK085 J
IK0910 J
IK1020 J
IK1150 J

For scale, 5 J (IK08) is a 1.7 kg mass dropped from 30 cm, and 20 J (IK10) is 5 kg from 40 cm. Cabinets for factory floors and outdoor sites are usually specified at IK08 or higher; luminaires in gyms and bus shelters at IK10. After the impact the enclosure must still meet its stated IP rating, so the two codes are checked together.

NEMA enclosure types

In the United States and Canada, enclosure types under ANSI/NEMA 250 (equipment up to 1000 V) are used instead of IP. A type covers not only dust and water but also corrosion, icing, oil and coolants.

Common NEMA 250 types
TypeIntended useApproximate IP
1indoor, protection against access and falling dirtIP10
3Routdoor: rain, snow, external ice formationIP14
3, 3Soutdoor: rain, windblown dust; 3S mechanisms stay operable when icedIP54
4indoor and outdoor, hose-directed waterIP66
4Xsame plus corrosion resistanceIP66
6, 6Ptemporary (6) and prolonged (6P) submersionIP67, IP68
12, 12Kindoor industrial: dust, fibers, dripping oil and liquidsIP52
13indoor industrial: sprayed oil and coolantIP54

Types 7, 8, 9 and 10 are for hazardous (classified) locations in the US and relate to explosion protection, not IP. European explosion-protection marking is covered in a separate article.

Why NEMA to IP works in one direction only

The approximate IP column means that an enclosure of a given NEMA type meets or exceeds that IP rating. The reverse does not hold. NEMA 4X tests corrosion resistance, gasket aging and icing, while IP66 requires none of these. An IP66 cabinet therefore does not automatically qualify as NEMA 4X, even if it withstands the same jets.

  1. Identify what actually threatens the equipment: dust, water, impacts, corrosion, ice, oil.
  2. For the EU and Ukrainian markets, specify IP under IEC 60529 and, where impacts are likely, IK under IEC 62262.
  3. If the customer documents call for a NEMA type, take the IP from the table as a minimum and check corrosion and icing separately.
  4. Remember that 7 and 8 do not replace 5 and 6: outdoor equipment that is hosed down needs IP66/IP67.
  5. Verify codes against the certificate or test report, not the catalog alone.