A cabinet, motor or luminaire nameplate usually carries two or three codes: IP66, IK08 and, on North American equipment, NEMA 4X as well. Each answers a different question. IP covers dust and water, IK covers impacts, and NEMA covers the environment as a whole, including corrosion and icing. That is why one code cannot simply be swapped for another.
The IP code: two digits and optional letters
The code is defined by IEC 60529. CIS countries use the identical GOST 14254-2015; Ukraine uses DSTU EN 60529. When a characteristic is not rated, an X takes its place: IPX4 means only splashing water was tested and no dust protection is claimed.
| Digit | Protection |
|---|---|
| 0 | none |
| 1 | objects over 50 mm (back of the hand) |
| 2 | over 12.5 mm (finger) |
| 3 | over 2.5 mm (tool) |
| 4 | over 1.0 mm (wire) |
| 5 | dust-protected: some dust enters but does not interfere with operation |
| 6 | dust-tight |
| Digit | Test |
|---|---|
| 0 | no protection |
| 1 | vertically dripping water |
| 2 | dripping water with the enclosure tilted up to 15° |
| 3 | spraying water up to 60° from vertical |
| 4 | splashing water from any direction |
| 5 | water jets (6.3 mm nozzle, 12.5 L/min) |
| 6 | powerful jets (12.5 mm nozzle, 100 L/min) |
| 7 | temporary immersion up to 1 m for 30 min |
| 8 | continuous immersion under conditions harder than 7, stated by the manufacturer |
| 9 | high-pressure, high-temperature jets (washdown) |
Digits 7 and 8 do not include 5 and 6. An enclosure that survives immersion can still leak under a jet, because the pressure acts differently. Outdoor equipment is therefore often dual-rated: IP66/IP67. The additional letters A–D show protection of persons against access to hazardous parts when it is higher than the first digit implies. The letters H, M, S and W describe the equipment itself: H for high-voltage apparatus, M and S for water tests with the equipment moving or stationary, W for specified weather conditions.
The IK code: impact energy
IEC 62262 rates enclosure resistance to external mechanical impacts for equipment up to 72.5 kV. The code always has two digits, from IK00 to IK10; a 2021 amendment added IK11. Behind each code is the impact energy in joules that the enclosure withstands without losing its protective properties.
| Code | Impact energy |
|---|---|
| IK00 | not rated |
| IK01 | 0.14 J |
| IK02 | 0.2 J |
| IK03 | 0.35 J |
| IK04 | 0.5 J |
| IK05 | 0.7 J |
| IK06 | 1 J |
| IK07 | 2 J |
| IK08 | 5 J |
| IK09 | 10 J |
| IK10 | 20 J |
| IK11 | 50 J |
For scale, 5 J (IK08) is a 1.7 kg mass dropped from 30 cm, and 20 J (IK10) is 5 kg from 40 cm. Cabinets for factory floors and outdoor sites are usually specified at IK08 or higher; luminaires in gyms and bus shelters at IK10. After the impact the enclosure must still meet its stated IP rating, so the two codes are checked together.
NEMA enclosure types
In the United States and Canada, enclosure types under ANSI/NEMA 250 (equipment up to 1000 V) are used instead of IP. A type covers not only dust and water but also corrosion, icing, oil and coolants.
| Type | Intended use | Approximate IP |
|---|---|---|
| 1 | indoor, protection against access and falling dirt | IP10 |
| 3R | outdoor: rain, snow, external ice formation | IP14 |
| 3, 3S | outdoor: rain, windblown dust; 3S mechanisms stay operable when iced | IP54 |
| 4 | indoor and outdoor, hose-directed water | IP66 |
| 4X | same plus corrosion resistance | IP66 |
| 6, 6P | temporary (6) and prolonged (6P) submersion | IP67, IP68 |
| 12, 12K | indoor industrial: dust, fibers, dripping oil and liquids | IP52 |
| 13 | indoor industrial: sprayed oil and coolant | IP54 |
Types 7, 8, 9 and 10 are for hazardous (classified) locations in the US and relate to explosion protection, not IP. European explosion-protection marking is covered in a separate article.
Why NEMA to IP works in one direction only
The approximate IP column means that an enclosure of a given NEMA type meets or exceeds that IP rating. The reverse does not hold. NEMA 4X tests corrosion resistance, gasket aging and icing, while IP66 requires none of these. An IP66 cabinet therefore does not automatically qualify as NEMA 4X, even if it withstands the same jets.
- Identify what actually threatens the equipment: dust, water, impacts, corrosion, ice, oil.
- For the EU and Ukrainian markets, specify IP under IEC 60529 and, where impacts are likely, IK under IEC 62262.
- If the customer documents call for a NEMA type, take the IP from the table as a minimum and check corrosion and icing separately.
- Remember that 7 and 8 do not replace 5 and 6: outdoor equipment that is hosed down needs IP66/IP67.
- Verify codes against the certificate or test report, not the catalog alone.