A motor nameplate carries a dozen abbreviations: IM B35, IP55, IC 411, Cl. F, S1, IE3. Each stands for a separate parameter, and a mistake in any of them gives you a motor that will not fit the base, overheats or fails the site conditions. Below: what each code means, where to find it on the nameplate and how to describe the motor so that a European equivalent can be selected without follow-up questions.

What is on the nameplate

Take a typical induction motor and read one nameplate line piece by piece:

132Mframe4poles7.5kWIM B35mountingIP55protectionIC 411coolingFinsulationS1duty
Main nameplate fields of an induction motor
FieldExampleWhat it means
Frame132MShaft centre height 132 mm; M is the medium frame length (S short, L long). The length sets the distance between the foot holes.
Poles / speed4 · 1455 min⁻¹Four poles means 1500 min⁻¹ synchronous speed at 50 Hz; rated speed is lower by the slip.
Power7.5 kWRated shaft output, not the power drawn from the supply.
Voltage and connection400 V Δ / 690 V YWindings in delta for 400 V or in star for 690 V. State the voltage of your own network.
MountingIM B35Feet and flange, horizontal shaft (see the mounting section).
ProtectionIP55Dust and water jets (see the IP section).
CoolingIC 411Totally enclosed motor with a shaft-mounted fan.
InsulationCl. FWinding thermal class 155 °C.
DutyS1Continuous operation at constant load.
Efficiency classIE3High efficiency class per IEC 60034-30-1.

Mounting: the IM code (IEC 60034-7)

The IM code answers two questions: are there feet and a flange, and is the shaft horizontal (letter B) or vertical (V). It is written in two ways: alphanumeric (IM B3) and four-digit numeric (IM 1001). Both appear on nameplates, so the table shows them side by side.

IM B3 · 1001IM B5 · 3001IM B35 · 2001IM B14 · 3601IM V1 · 3011IM V3 · 3031
Fig. 1. Main mounting arrangements (side view, shaft to the right or down/up). Each is labelled with both IEC 60034-7 notations.
Main mounting arrangements per IEC 60034-7
CodeNumeric codeWhat it is
IM B31001foot-mounted, horizontal shaft, feet down
IM B53001no feet, large flange FF with through holes
IM B352001feet and large flange FF
IM B143601no feet, small flange FT with tapped holes
IM B342101feet and small flange FT
IM V13011large flange, shaft down
IM V33031large flange, shaft up
IM V51011feet, wall-mounted, shaft down
IM V61031feet, wall-mounted, shaft up
IM V183611small flange, shaft down
IM V193631small flange, shaft up

Motors from CIS countries often carry GOST 2479 codes: IM1081, IM2081, IM3081, IM3681. They map to IM B3, B35, B5 and B14 respectively.

Position matters A B3 motor cannot simply be stood on end: bearings, grease and water protection are designed for a specific shaft position. Vertical arrangements (V1, V3 and others) are ordered separately by code.

Frame size, shaft and flanges

Frame size is the shaft centre height above the mounting plane in millimetres (132 mm for a 132M motor). Together with the length letter (S, M, L) it fixes the distance between the foot holes, and IEC 60072 also fixes the shaft diameter and length and the flange size. That is why a European motor of the same frame and length fits the same feet as an AIR-series motor of that frame.

HEDBB — distance between foot-hole centres along the shaftH — shaft centre height above the mounting planeE — length of the shaft extensionD — shaft diameter
Fig. 2. Mounting dimensions of a foot-mounted motor: H, D, E, B.
Typical motor dimensions: frame, shaft and flanges
Frame H, mmShaft D, mmFlange FF (B5)Flange FT (B14)
7114FF130FT85
8019FF165FT100
9024FF165FT115
100 / 11228FF215FT130
13238FF265FT165
16042FF300—
18048FF300—

These are typical values for common designs; check exact dimensions against the catalogue sheet. For foot-mounted motors H, the hole spacings A and B, shaft diameter D and length E must match; for flange motors, the spigot diameter, the bolt circle and the shaft diameter.

Ingress protection IP and impact rating IK

Two digits follow the letters IP. The first (0–6) is protection against solid objects and dust, the second (0–9) against water. The ones you meet most often on motors:

Common motor protection degrees
CodeSolidsWater
IP23objects over 12 mmdrops at up to 60° (open motor)
IP54dust partlysplashing from any direction
IP55dust partlywater jets
IP56dust partlypowerful jets
IP65dust-tightwater jets
IP66dust-tightpowerful jets

IP55 is the standard for modern motors. For pressure washing or a dusty workshop choose IP65–IP66. The IK impact rating (IEC 62262) is rarely marked on motors. Standard conditions under IEC 60034-1: ambient up to 40 °C, altitude up to 1000 m. In heat or at altitude the motor is derated, so state the real conditions in the enquiry.

Cooling: the IC code

The IEC 60034-6 code describes how the heat is removed. The most common ones:

Main cooling methods
CodeCooling method
IC 01open motor, self-ventilated
IC 06open motor, separate fan with its own drive
IC 410enclosed, no fan, the frame sheds the heat
IC 411enclosed, shaft-mounted fan (the most common)
IC 416enclosed, separate fan with its own drive
IC 81Wenclosed, water jacket
Motor on a frequency converter At low speed a shaft-mounted fan cools poorly. If the motor runs from a converter at high load and low speed, order IC 416 (separate fan) or derate the load.

Insulation, duty and efficiency class

The insulation class shows what temperature the winding withstands, not what it reaches in service.

Insulation thermal classes
ClassMaximum temperaturePermitted rise at 40 °C
B130 °C80 K
F155 °C105 K
H180 °C125 K

A common European combination is class F insulation with a class B temperature rise, which leaves a margin in temperature and service life.

Duty S1–S10 under IEC 60034-1 describes how the load varies over time. A wrong duty is one of the most frequent causes of overheating.

Duty types
DutyLoad pattern
S1continuous, constant load
S2short-time (10, 30, 60, 90 min), then the motor cools down
S3intermittent, starting does not affect heating; the cyclic duration factor is specified
S4–S5intermittent with frequent starts; S5 adds electric braking
S6–S8continuous with periodic load, starting and braking
S9–S10non-periodic or discrete loads

The efficiency class IE1–IE4 (IEC 60034-30-1) is the motor efficiency. IE3 or better is required for new motors in the EU, so a European equivalent usually has higher efficiency than an old motor with a CIS data sheet.

DC motors

In a DC motor the excitation circuit matters as well: it decides how the motor behaves under load and how its speed is controlled.

M+−A1A2F1F2SeparateM+−A1A2E1E2ShuntM+−D1D2A1A2SeriesM+−A1A2D1D2E1E2Compound
Fig. 3. Connection diagrams and terminal marking per IEC 60034-8: A — armature, D — series field, E — shunt field, F — separate field.
Excitation circuits of DC motors
ExcitationTerminalsCharacteristics
SeparateA1–A2, F1–F2the field is supplied separately; stable speed, controlled by armature voltage or field current
ShuntA1–A2, E1–E2field in parallel with the armature; stiff characteristic, simple machine-tool and fan drives
SeriesA1–A2, D1–D2field in series with the armature; high starting torque (traction, hoists), races without load so it must never run unloaded
CompoundA, D, Ecombination of shunt and series windings; a compromise between torque and speed stability

Terminal marking per IEC 60034-8: A — armature, B — commutating poles, C — compensating winding, D — series field, E — shunt field, F — separate field. DC motors usually have forced ventilation (IC 06 or IC 416), and the speed sensor (tacho-generator, encoder) is a separate item.

CIS designations and the European equivalent

The abbreviations in old data sheets have direct IEC counterparts.

CIS designations mapped to IEC
On the data sheetMeaningIEC term
АИР100L4, 4А, 5Аinduction series with IEC frame sizesframe 100L, 4 poles, the same mounting dimensions
IM1081, IM2081, IM3081arrangement per GOST 2479IM B3, B35, B5
У2, У3, УХЛ4climatic versionconditions per IEC 60034-1: temperature and altitude; protection is given by the IP code
ПВ 40 %cyclic duration factorduty S3 with a 40 % load factor in the cycle
380 Vsupply voltage400 V ±10 % is the European motor voltage; check the nameplate
2П, 4П, ПБСDC motorsIEC DC motors with the same shaft height and excitation scheme

What to state in a motor enquiry

So that the supplier can select an equivalent without follow-up questions, collect these from the nameplate or data sheet:

  1. Power in kW and the number of poles or rated speed.
  2. Voltage, frequency, winding connection.
  3. Frame with the length letter (for example 132M) or the old series designation.
  4. Mounting: IM B3, B5, B35, V1 and so on, and the shaft position.
  5. Shaft: diameter and length, keyway; flange, if there is one.
  6. IP rating, IC cooling method, altitude and ambient temperature.
  7. Duty S and the supply: mains or frequency converter.
  8. Extras: thermal protection (PTC, PT100), heater, encoder, brake, explosion protection (a separate subject).
  9. A photo of the nameplate: most parameters can be recovered from it.

Where to select

Motors from stock and to order are in the catalogue (section “Electric motors”); low-voltage motors and drives are on ukrsk.com.ua (Ukrainian page). On selecting replacements for other equipment see How to read ТМГ, ТСЗ, ТДН designations and the guide to supplying equipment from the EU.

Codes and classes are given per the IEC 60034 series and IEC 60072. Exact values for a given motor are set by its catalogue sheet.