Most substations in Ukraine still run transformers with designations like ТМ-630/10 (TM) or ТСЗ-400/10 (TSZ). The designation tells you a lot: cooling type, rating, voltage class, climate category. But it isn’t enough to order a replacement, and the parameters it leaves out are what most often derail schedules.

How a designation is built

A power transformer designation consists of a letter code, the rating, the voltage class and the climate category. Here is an example broken down:

ТphasesМcoolingГversion11series1000kVA10kV HVУ1climate

Three-phase (Т, T), oil-immersed with natural cooling (М, M), hermetically sealed with no conservator (Г, G), design series 11, rated 1,000 kVA, HV winding voltage class 10 kV, for a temperate climate and outdoor installation (У1, U1). The letters always come in the same order:

Order of letters in a power transformer designation
PositionLettersMeaning
TypeАautotransformer; no letter means a conventional transformer
Number of phasesО, Тsingle-phase; three-phase
LV windingРsplit into two sections
CoolingМ, Д, ДЦ, Ц, С, СЗ, СГoil, natural; oil with forced air; forced air and forced oil circulation; oil-to-water; dry, open; dry, protected; dry, sealed
Number of windingsТthree windings; no letter means two
Voltage regulationНon-load tap changing (OLTC, РПН); no letter means off-circuit tap changing (ПБВ)
Special featuresГ, З, Л, С, Жhermetically sealed; protected; cast-resin insulation; for power plant auxiliaries; for railway traction substations

So ТДТН (TDTN) is three-phase, forced-air cooled, three-winding, with OLTC, and ТРДН (TRDN) is three-phase with a split winding, forced-air cooling and OLTC. Current and voltage transformers (ТОЛ, ТПЛ, НАМИ, ЗНОЛ, or TOL, TPL, NAMI, ZNOL) follow a different system; the decoder below recognizes them by series name.

Designation decoder

Enter the designation from the nameplate or a diagram. Latin letters that look like Cyrillic ones are converted automatically.

DecoderDesignations of transformers, КТП (KTP) packaged substations, CTs and VTs

Examples:

The decoder follows the general designation rules. Some manufacturers added their own letters and indices, so always check the result against the data sheet.

What the designation leaves out

From the designation ТМ-630/10 you can tell it’s a three-phase oil-immersed 630 kVA transformer for 10 kV networks. That isn’t enough to order a replacement. Here is what else you need, and it’s usually all on the nameplate:

ParameterWhere to find itWhy it matters
Winding connection and vector groupnameplate: Y/Yн-0, Д/Yн-11 (Yyn0, Dyn11 in IEC notation)determines parallel operation and behavior under unbalanced load
LV voltagenameplate: 0.4 or 0.69 kVthe “/10” in the designation is only the high-voltage side
Short-circuit voltage, uknameplate, %fault currents on the 0.4 kV busbars and load sharing in parallel operation
Off-circuit (ПБВ) or on-load (РПН) tap rangenameplate, for example ±2×2.5%whether voltage at the consumers can be maintained
Dimensions, weight, wheel gaugedata sheet or tape measurewhether the new transformer will fit in the КТП bay or on the foundation
Bushing type and connectionsphotosbusbars, cable, cable terminations, bushing layout

Y/Yн-0 or Dyn11: the main trap

Many distribution transformers in rural and urban networks are connected star–star with neutral (Y/Yн-0). In Europe, the standard for distribution transformers is delta–star with neutral (Dyn11). For a new site, Dyn11 is the better choice: it copes better with unbalanced single-phase loads and suppresses third harmonics. For a Y/Yн-0 transformer, the electrical installation rules limit the neutral current to 25% of rated current.

Parallel operation Transformers with different vector groups must not be connected in parallel: there is a phase shift between their secondary voltages, and circulating currents close to short-circuit levels will flow in the loop. If a substation has two Y/Yн-0 transformers running in parallel and you’re replacing one, order a Y/Yн-0 unit or replace both. European factories build Y/Yн-0 units to order, but you have to state this requirement explicitly.

For parallel operation, besides the vector group, the voltage ratio and the short-circuit voltage must match (uk within 10%), and the power ratio should preferably not exceed 1:3.

Dimensions and connections

Modern low-loss transformers are often heavier and larger than the old ones: reducing losses takes more steel and copper. The reverse also happens: a sealed transformer with no conservator is shorter than its predecessor. Either way, check the bay dimensions, doors, wheel gauge and clearances to the walls before you order.

Bushing layout matters too. In older КТП substations, the busbars are designed for a specific position of the insulators on the cover. If the new transformer’s bushings are placed differently, you’ll need new busbars or a switch to cable, and that should go into the budget.

Fittings

A transformer with a conservator is protected by a gas (Buchholz) relay; a sealed one, by a pressure relay or a combined device on the cover. If the substation already has a gas protection circuit, check that the new transformer’s fittings are compatible with it. Equivalents of the РЗТ (RZT) and РГТ (RGT) gas relays are in the transformer fittings section.

What to send us to find a replacement

  1. A photo of the nameplate, sharp enough that every number is legible.
  2. A photo of the whole transformer and close-ups of the bushings.
  3. Dimensions of the installation space: bay, doors, foundation.
  4. Operating mode: standalone or in parallel with another transformer, average and maximum load.
  5. Grid requirements: technical connection conditions or correspondence with the grid operator, if the rating is changing.

For series that already have catalog pages with European equivalents, the decoder shows a link. The full list is in the distribution, power and instrument transformer sections.

Discuss your project

Tell us about your challenge. We will help you find the right direction and define your next step.