A cable from a GOST cable schedule often has to be replaced with a European or Chinese one, and the other way round. The letter codes in all three systems describe the same things: conductor material, insulation, screen, armor, sheath and fire behavior. The order and the letters differ, so decode the cable element by element rather than looking for a similar string of characters.
GOST: from conductor to sheath
| Letter | Meaning |
|---|---|
| А / A (first) | aluminum conductor |
| В / V | PVC insulation or sheath |
| П, Пв / P, Pv | polyethylene, cross-linked polyethylene |
| Б, Бб / B, Bb | steel tape armor |
| К / K (first) | control cable |
| Г / G | no protective covering over the armor or sheath |
| Шв, Шп / Shv, Shp | PVC or polyethylene outer jacket |
| нг(А), нг(А)-LS, нг(А)-HF, нг(А)-FRLS | flame retardant in bundles (category A), low smoke, halogen-free, fire resistant |
VDE and HD 361: German types and harmonized cables
German type codes are still widely used for power cables in Europe. A leading N means the cable follows a VDE standard; the following letters run from the conductor outward.
| Letter | Meaning |
|---|---|
| A | aluminum conductor |
| Y | PVC |
| 2X | cross-linked polyethylene (XLPE) |
| 2Y | thermoplastic polyethylene |
| S, SE | copper screen, common or per phase |
| (F) | longitudinally watertight screen |
| B, FG | steel tape armor, flat steel wire armor |
| HX | halogen-free sheath |
NA2XS(F)2Y 1×240RM/25 6/10 kV reads as aluminum conductor, XLPE insulation, longitudinally watertight copper screen and polyethylene sheath. Flexible and wiring cables are harmonized under HD 361: H07RN-F is harmonized (H), 450/750 V (07), rubber insulation (R), polychloroprene sheath (N) and flexible conductor (F). H05VV-F is 300/500 V with PVC insulation and sheath.
GB: Chinese designations
In the Chinese system YJ stands for XLPE insulation, V for PVC, Y for polyethylene and L for an aluminum conductor. Two trailing digits give armor and outer covering: 22 for steel tape with a PVC sheath, 23 for steel tape with polyethylene, 32 for fine steel wire with PVC. The prefixes ZR (ZA, ZB, ZC are categories), NH and WDZ mean flame retardant, fire resistant, and low-smoke halogen-free respectively.
Nearest equivalents
| GOST | VDE | GB | Construction |
|---|---|---|---|
| VVG (ВВГ) | NYY | VV | copper, PVC, PVC, up to 1 kV |
| AVVG (АВВГ) | NAYY | VLV | aluminum, PVC, PVC |
| VBbShv (ВБбШв) | NYBY | VV22 | copper, PVC, steel tape, PVC |
| PvV (ПвВ) | N2XY | YJV | copper, XLPE, PVC, 0.6/1 kV |
| APvV (АПвВ) | NA2XY | YJLV | aluminum, XLPE, PVC |
| PvBbShv (ПвБбШв) | — | YJV22 | copper, XLPE, armor, PVC |
| APvPu (АПвПу), 6–35 kV | NA2XS(F)2Y | YJLY | aluminum, XLPE, copper screen, polyethylene |
| KVVG (КВВГ) | — | KVV | control, copper, PVC |
The table matches construction, not certification. GOST fire categories (ng(A), LS, FRLS) and the European reaction-to-fire classes under EN 50575 (Cca, B2ca and others) are tested by different methods and do not translate directly.
- Match the rated voltage U0/U (0.6/1 kV, 6/10 kV, 8.7/15 kV, 12/20 kV), not just the network class.
- Compare conductor and screen cross-sections: for short-circuit current, 16 and 35 mm² screens differ a lot.
- Check conductor shape (round, sector, compacted RM/SM) and flexibility class.
- Direct burial and wet routes need longitudinal water blocking and a suitable sheath.
- Check fire requirements against the certificate, not against similar letters.