SION 3AE2 / 3AK7 — compact vacuum circuit breakers for generator circuits up to 17.5 kV

SION 3AE2 and 3AK7 vacuum circuit breakers for medium-voltage generator circuits up to 17.5 kV with a rated current of up to 4000 A. Breaking current reaches 31.5 kA for the 3AE2 and 50 kA for the 3AK7. Both types have passed tests to the generator standard IEC/IEEE 62271-37-013.

SION 3AE2
up to 17.5 kV; up to 31.5 kA; up to 4000 A; fixed-mounted or withdrawable
3AK7
up to 17.5 kV; up to 50 kA; up to 4000 A; 30,000 cycles
Tests
IEC 62271-100, IEC/IEEE 62271-37-013 (generator standard)
3AK7 purpose
generator switching, transfer of high-power loads, frequent operations

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Interrupting short-circuit currents near a generator is among the hardest tasks in medium-voltage networks. Such currents have a large aperiodic component, and the current zero crossing is delayed. SION 3AE2 and 3AK7 are compact vacuum circuit breakers for generator circuits. Both have passed type tests to the demanding generator standard IEC/IEEE 62271-37-013, which confirms their ability to perform such switching.

Unlike specialized high-power generator circuit breakers (3AH36/37/38), these devices are compact and fit standard switchgear panels. SION 3AE2 is part of the SION platform. It is rated for voltage up to 17.5 kV, breaking current up to 31.5 kA and rated current up to 4000 A, and is available fixed-mounted and withdrawable. Despite its generator ratings, it is just as narrow as breakers for standard applications and is compatible with all SION accessories, so it can be placed in the same compact switchgear together with other breakers of the family.

3AK7 is a compact all-in-one breaker for generator switching, transfer of high-power loads and frequent operations. Voltage is up to 17.5 kV, breaking currents up to 50 kA, rated currents up to 4000 A. It is tested to IEC 62271-100 and IEC/IEEE 62271-37-013 and withstands 30,000 operating cycles even under an intensive switching schedule. For the 3AK7, a catalog, operating instructions, drawings, 3D models and diagrams, and an online configurator are available.

Applications include generator circuits of small and medium power plants (gas-engine, gas-turbine and steam-turbine CHP plants, small hydro), industrial power plants, auxiliary-supply switchgear, and systems with frequent load transfer.

Technical specifications

SION 3AE2up to 17.5 kV; up to 31.5 kA; up to 4000 A; fixed-mounted or withdrawable
3AK7up to 17.5 kV; up to 50 kA; up to 4000 A; 30,000 cycles
TestsIEC 62271-100, IEC/IEEE 62271-37-013 (generator standard)
3AK7 purposegenerator switching, transfer of high-power loads, frequent operations

Request a price and lead time

SION 3AE2 / 3AK7 — compact vacuum circuit breakers for generator circuits up to 17.5 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which test confirms suitability for generator circuits?

Type tests to IEC/IEEE 62271-37-013 on breaking short circuits near a generator. The 3AK7 is also tested to IEC 62271-100.

What breaking current do the 3AE2 and 3AK7 have?

The 3AE2 breaks up to 31.5 kA, the 3AK7 up to 50 kA. The rated current of both is up to 4000 A.

How does the 3AK7 differ from the 3AE2 in purpose?

The 3AK7 is designed for generator switching, transfer of high-power loads and frequent operations, with an endurance of 30,000 cycles. The 3AE2 is available fixed-mounted and withdrawable for voltage up to 17.5 kV.