SF6 load break switches for overhead lines 15.5–36 kV

SF6 load break switches for overhead lines of 15.5, 25.8 and 36 kV with puffer-type arc extinction and a spring toggle drive. Withstand current up to 16 kA, service life 5000 operations, and the motorized version with the ETMFC610 controller works in loop automation.

Rated voltage
15.5; 25.8; 36 kV
Short-time withstand current
16 kA (15.5 kV); 12.5 kA, 1 s
Making capacity
41.6 / 32.5 kA (peak)
Insulation (36 kV)
170 kV impulse; 70 kV dry; 45 kV wet

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The three-phase SF6 load break switches operate on overhead lines of the 15.5, 25.8 and 36 kV classes. The 15.5 kV model passed type tests at CESI in 2014–2015, and the whole series was tested at KEMA, CESI or KERI to IEC 62271-103.

The drive is built on a spring toggle mechanism, so the closing and opening speed does not depend on the operator. The arc is extinguished by SF6 on the self-compression (puffer) principle. The bushings are epoxy with a silicone housing. The switch tank and the control cabinet are made of stainless steel and withstand heat, humidity, dust and corrosive environments. The device is operated manually or by a built-in motor drive, with a declared service life of 5000 operations.

Frequency is 50/60 Hz. Short-time withstand current is 16 kA for 15.5 kV and 12.5 kA for 1 s for 25.8 and 36 kV, with making capacity of 41.6 and 32.5 kA (peak) respectively. The 36 kV class insulation is rated for 170 kV impulse, 70 kV power frequency dry and 45 kV wet. The control circuits are powered from 110–220 V AC or 24 V DC, with a test voltage of 2 kV and an impulse of 6 kV. Operating temperature is −25…+70 °C.

The motorized version is supplied with the microprocessor controller ETMFC610, which measures, monitors and records parameters and supports communication, with a built-in RTU or separate digital control. For these LBS the company also offers the multifunction controller ETMFC101-N1 with RTU. It measures voltage, current and power, monitors phase loss and synchronism, blocks closing under load and shows faults by phase, zero-sequence and negative-sequence currents. The protocols are DNP3.0, MODBUS and IEC 60870-5-101/104, with support for PLC, PQM, GPS, IRIG and SMS.

With such a controller the switch becomes an automatic sectionalizer or a normal open point in loop automation schemes and is controlled remotely from SCADA. The switches are installed for sectionalizing and backup of 10–35 kV overhead networks, on taps to consumers and generation, in distribution automation systems.

Technical specifications

Rated voltage15.5; 25.8; 36 kV
Short-time withstand current16 kA (15.5 kV); 12.5 kA, 1 s
Making capacity41.6 / 32.5 kA (peak)
Insulation (36 kV)170 kV impulse; 70 kV dry; 45 kV wet
Arc extinctionself-compression (puffer) in SF6
Drivespring toggle; manual or motorized
Service life5000 operations
ControllerETMFC610 / ETMFC101-N1
Temperature−25…+70 °C
StandardsIEC 62271-103 (type), ANSI C37.60, IEC 62271-111

Request a price and lead time

SF6 load break switches for overhead lines 15.5–36 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8535 30 10 00
HS, 6 digits8535 30
CN (EU)8535 30 10
HTSUS (USA)8535 30 00 80
China customs tariff8535 30 00 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which voltage classes are the SF6 load break switches rated for?

The series covers 15.5, 25.8 and 36 kV at 50/60 Hz. Typical use is in 10–35 kV overhead networks.

What short-time withstand current does the switch have?

The 15.5 kV model withstands 16 kA, the 25.8 and 36 kV models 12.5 kA for 1 s. Making capacity is 41.6 and 32.5 kA (peak).

How does the switch work in network automation?

With the ETMFC610 or ETMFC101-N1 controller it becomes an automatic sectionalizer or a normal open point. Communication with SCADA runs over DNP3.0, MODBUS and IEC 60870-5-101/104.