RLSwitcher SF6 shunt reactor switch, 36–550 kV
RLSwitcher SF6 switch for shunt reactor switching at 36–550 kV, rated current up to 3000 A. It breaks inductive current up to 1600 A and short-circuit current up to 40 kA.
- Rated voltage
- 36–550 kV
- Rated current
- up to 3000 A
- Breaking current
- up to 1600 A (inductive)
- Short-circuit breaking current
- up to 40 kA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The unit has a special SF6 chamber that limits the transient recovery voltage (TRV) when the reactor is switched off. This reduces the probability of restrikes in the chamber after an inductive current is interrupted. The switch is installed in shunt reactor feeders at HV and EHV substations.
Technical specifications
| Rated voltage | 36–550 kV |
|---|---|
| Rated current | up to 3000 A |
| Breaking current | up to 1600 A (inductive) |
| Short-circuit breaking current | up to 40 kA |
| Arc extinction | SF6, a chamber that limits TRV |
Request a price and lead time
RLSwitcher SF6 shunt reactor switch, 36–550 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8535 29 00 00 |
|---|---|
| HS, 6 digits | 8535 29 |
| CN (EU) | 8535 29 00 |
| HTSUS (USA) | 8535 29 00 40 8535 29 00 20 |
| China customs tariff | 8535 29 10 00 8535 29 20 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
How does the RLSwitcher differ from an ordinary circuit breaker?
Its chamber limits the transient recovery voltage and the probability of restrikes when a reactor is switched off.
What inductive current does the RLSwitcher break?
Up to 1600 A, with a rated current of up to 3000 A.
What voltage is the RLSwitcher made for?
36–550 kV, with a short-circuit breaking current up to 40 kA.