International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

INEXT outdoor SF6 load break switch 24/36 kV for overhead lines (including remote-controlled)

An outdoor switch-disconnector with arc extinction in SF6 gas for 24 and 36 kV, mounted on overhead line poles, with a manual or motorized remote-controlled drive. Rated current 400–630 A, short-circuit making capacity 50 kA. Used for sectionalizing overhead lines, on branches and at overhead-to-cable transition points.

Rated voltage
24 and 36 kV
Rated current
400–630 A (24 kV), 400 A (36 kV)
Breaking
630 / 400 A load and loop; cables/lines 25 / 40 A
Making capacity
50 kA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

INEXT is a switch-disconnector with arc extinction and insulation in SF6 gas for outdoor installation on poles of medium voltage overhead distribution lines of any type. It is used for disconnecting and sectionalizing an overhead line, on branches, and at points where an overhead line transitions to a cable line. The stainless steel enclosure contains the arc-quenching chambers, busbar terminals, a spring mechanism and the SF6 gas. The device is designed for snow, ice, wind, rain and industrial pollution.

The tank is sealed for life under the 'sealed pressure system' criterion of IEC 62271-200 with a minimum SF6 leakage rate. The bushings in a polymer housing have a creepage distance of 780 mm (24 kV) and 1050 mm (36 kV). The operating mechanism is housed in a separate stainless steel enclosure rigidly connected to the switch. Switching on and off is performed by a single spring regardless of the speed of the operator's actions. The two-position scheme provides natural interlocking, and the load break and disconnecting functions are combined. A retroreflective position indicator is clearly visible from the ground (IEC 62271-102).

The device meets classes E3 and M2 and is made for 24 and 36 kV. The one-minute withstand voltage is 50/60 and 70/80 kV, the impulse voltage 125/145 and 170/195 kV. Rated current is 400–630 A and 400 A respectively, short-time withstand current 20 kA. Breaking of active load and closed loop is 630 / 400 A, cable and line charging currents 25 / 40 A, short-circuit making 50 kA. SF6 pressure is 0.13 and 0.18 MPa abs., weight 105 and 112 kg. Operating temperature is −25…+60 °C, altitude up to 1000 m, tank IP67, drive IP55.

Operation is possible with a hook stick from the ground, a manual cable drive MMT / MMT-MS (stainless steel cables, intermediate ceramic insulators, a handle near the base of the pole), or a pull-rod drive MPH with rods up to 12 m. The motorized INEXT (OCR) has remote control: a 48 V DC motor (optionally 12–24 V) rated 250 W, a control cabinet near the pole with a battery, current transformers on the input (optionally on the output), a single-phase VT or voltage sensors, a cable up to 17 m and remote control. Options are surge arresters, a low pressure lockout and a bracket. Applications include automation of 10–35 kV overhead distribution networks, sectionalizing of main lines, and connection of taps and cable sections.

Technical specifications

Rated voltage24 and 36 kV
Rated current400–630 A (24 kV), 400 A (36 kV)
Breaking630 / 400 A load and loop; cables/lines 25 / 40 A
Making capacity50 kA
Short-time withstand20 kA
Insulation50/60 and 125/145 kV (24 kV); 70/80 and 170/195 kV (36 kV)
SF6 pressure0.13 / 0.18 MPa abs.
ClassesE3, M2
Weight105 / 112 kg
Temperature−25…+60 °C
Protection degreetank IP67, drive IP55
StandardsIEC 62271-100/102/103/200, IEC 60044-1/2

Request a price and lead time

INEXT outdoor SF6 load break switch 24/36 kV for overhead lines (including remote-controlled). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltages and currents is INEXT made for?

For 24 and 36 kV, with a rated current of 400–630 A for 24 kV and 400 A for 36 kV. Short-time withstand current is 20 kA, short-circuit making 50 kA.

What control options are available?

A hook stick from the ground, a manual cable drive MMT / MMT-MS, a pull-rod drive MPH with rods up to 12 m, or a motorized drive with a 48 V DC motor rated 250 W and remote control.

What standards is the device made to and what is its protection degree?

Standards IEC 62271-100/102/103/200 and IEC 60044-1/2. The tank has protection degree IP67, the drive IP55.

Similar equipment from other manufacturers