GZHV and high-voltage miniature fuses up to 10 kV for measuring circuits
GZHV cylindrical high-voltage miniature fuses for voltages from 1.2 to 10 kV for measuring circuits. Rated current is 0.032–16 A, with F and T characteristics, and breaking capacity of 35 A, 1.5 kA, 10 kA or 30 kA depending on the group. Sizes are 8×50, 8×65, 8×85, 8×120, 8×150 and 10×85 mm.
- Sizes
- 8×50, 8×65, 8×85, 8×120, 8×150, 10×85 mm
- Rated voltage
- AC 1.2; 3; 6; 10 kV; AC 1.5 kV / DC 1 kV; DC 1.5 kV
- Rated current
- 0.032–16 A
- Characteristics
- F, T
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
GZHV high-voltage miniature fuses are cylindrical low-current fuse-links for voltages from 1.2 to 10 kV. They are used to protect measuring equipment, test equipment in distribution networks, measuring transformers and auxiliary circuits with high voltage. They fill the gap between HH fuse-links for power circuits and ordinary GS miniature fuses.
The range includes several groups. The GZHV 10×85 mm version F (fast-acting) for 1–16 A, AC 1500 V / DC 1000 V, with a breaking capacity of 1.5 kA at AC 1.5 kV and 300 A at DC 1000 V (series 7011552). The version T (time-delay) for 0.63–12.5 A, AC 1500 V / DC 1000 V, 10 kA at DC 900–1000 V (series 7011527). The version F for 0.125–4 A and AC 3000 V (series 7011509).
For high-voltage AC circuits, fuse-links 8×50 mm (0.032–10 A, 1200 V), 8×85 mm (0.032–4 A, 3 kV), 8×120 mm (0.032–4 A, 6 kV) and 8×150 mm (0.032–2 A, 10 kV) are produced, with F characteristic and a breaking capacity of 35 A. For direct current, fuse-links 8×65 mm for 0.5–3.15 A, DC 1.5 kV, 30 kA are intended. For powerful measuring applications, 10×38 mm gR fuse-links, AC/DC 1000 V, 30 kA are also offered.
The design has robust ceramic and optimised fuse elements with low self-heating. For mounting, holders, URZ-C clips with screw fixing and 10×14 mm pressure plates are supplied. Fuse-links are selected by measurement categories CAT I–CAT IV under IEC 61010. The closer the measuring point is to the source, the higher the short-circuit current and the energy of transients.
They are used to protect measuring transformers and voltmeters in switchgear cubicles, in test and diagnostic installations for medium voltage networks, in high-voltage power supply units, traction equipment, and converters of photovoltaic and storage systems. VDE, UL, CSA and SEMKO certificates confirm international applicability.
Technical specifications
| Sizes | 8×50, 8×65, 8×85, 8×120, 8×150, 10×85 mm |
|---|---|
| Rated voltage | AC 1.2; 3; 6; 10 kV; AC 1.5 kV / DC 1 kV; DC 1.5 kV |
| Rated current | 0.032–16 A |
| Characteristics | F, T |
| Breaking capacity | 35 A at AC 1.2–10 kV; 1.5 kA AC 1.5 kV / 300 A DC 1 kV (GZHV F); 10 kA DC 900–1000 V (GZHV T); 30 kA DC 1.5 kV (8×65) |
| Accessories | URZ-C holders, contact clips, pressure plates |
Request a price and lead time
GZHV and high-voltage miniature fuses up to 10 kV for measuring circuits. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltages and currents are GZHV miniature fuses designed for?
Voltages from 1.2 to 10 kV and rated current from 0.032 to 16 A. Sizes are 8×50, 8×65, 8×85, 8×120, 8×150 and 10×85 mm.
What is the breaking capacity of AC and DC fuse-links?
The 8×50, 8×85, 8×120 and 8×150 mm AC fuse-links have 35 A. The GZHV 10×85 mm version F has 1.5 kA at AC 1.5 kV and 300 A at DC 1000 V, version T has 10 kA at DC 900–1000 V, and the 8×65 mm fuse-links for DC 1.5 kV have 30 kA.
By which measurement categories are these fuse-links selected?
By categories CAT I–CAT IV under IEC 61010. The closer the measuring point is to the source, the higher the short-circuit current and the energy of transients.