EPR / EPRIS — solid epoxy insulated reclosers 15.5–38 kV
EPR and EPRIS are vacuum reclosers with solid epoxy insulation for overhead lines and substations of 15.5, 27 and 38 kV, with rated current up to 800 A and breaking current up to 16 kA. The magnetic actuator drive withstands 10 000 operations, and the ETR300-R or EVRC2A-NT controller provides protection and a SCADA link.
- Rated voltage
- 15.5 kV (1-phase EPRIS and 3-phase), 27 kV, 38 kV
- Rated current
- 630/800 A; 800 A
- Breaking current
- 16 kA (27 kV — 12.5/16 kA)
- Short-time withstand
- 16 kA, 3 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The line consists of the three-phase reclosers EPR-1, EPR-2, EPR-3 and the single-phase EPRIS. They are installed on overhead lines and substations of the 15.5, 27 and 38 kV classes. In 2002 the company was the first in Korea to make a 27 kV solid-insulated recloser that passed type tests at KEMA, and later added 15 and 38 kV models.
The arc is extinguished by vacuum interrupters cast into epoxy bushings. There is no oil or gas inside, so there is no explosion hazard. The bushings are made of hydrophobic cycloaliphatic epoxy resin HCEP (Hydrophobic Cycloaliphatic Epoxy), keep insulating properties in harsh climates and heavily polluted areas, and resist tracking, ultraviolet and vandalism. The creepage distance meets ANSI. The stainless steel tank and control cabinet withstand heat, humidity, dust and corrosion. The drive is built on a permanent magnet actuator PMA without mechanical latches, with few moving parts and a life of 10 000 operations without maintenance.
The single-phase version is rated for 15.5 kV, the three-phase ones for 15.5, 27 and 38 kV. Rated current is 630/800 A and 800 A. Breaking and short-time withstand current is 16 kA for 3 s, and for 27 kV it is 12.5 or 16 kA. Making capacity is 41.6 kA, and in the 27 kV model 32.5/41.6 kA. Cable charging current is interrupted within 10–40 A, line charging current within 2–5 A. The insulation of the 38 kV unit withstands an impulse of 170 kV, 70 kV dry and 45 kV wet.
The tank has built-in resistive (1 %) and capacitive (2.5 %) voltage dividers and CTs for the whole protection range, and manual tripping is provided. The 17 A·h battery gives hundreds of operations with supply lost for up to 30 hours. Supply is 110–240 V AC or 125 V DC, temperature range is −40…+80 °C, degree of protection is IP65.
Microprocessor controllers ETR300-R or EVRC2A-NT have a built-in RTU, measurement, an event log and communication over DNP 3.0, MODBUS, IEC 60870-5-101/104, and the ETR300-R also works over IEC 61850. Functions 51P/51G/50P/50G/46/81/27/59/67/79 are implemented. The recloser is mounted on a pole or at a substation, accessories included. Type tests were carried out at KEMA, CESI and KERI to ANSI/IEEE C37.60 and IEC 62271-111.
Technical specifications
| Rated voltage | 15.5 kV (1-phase EPRIS and 3-phase), 27 kV, 38 kV |
|---|---|
| Rated current | 630/800 A; 800 A |
| Breaking current | 16 kA (27 kV — 12.5/16 kA) |
| Short-time withstand | 16 kA, 3 s |
| Making capacity | 41.6 kA (27 kV — 32.5/41.6 kA) |
| Charging current breaking | cables 10–40 A; lines 2–5 A |
| Insulation (38 kV) | 170 kV impulse; 70 kV dry, 45 kV wet |
| Drive | magnetic actuator PMA, 10 000 operations |
| Controller | ETR300-R or EVRC2A-NT |
| Temperature | −40…+80 °C |
| Degree of protection | IP65 |
| Standards | ANSI/IEEE C37.60, IEC 62271-111 |
Request a price and lead time
EPR / EPRIS — solid epoxy insulated reclosers 15.5–38 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8535 21 00 00 |
|---|---|
| HS, 6 digits | 8535 21 |
| CN (EU) | 8535 21 00 |
| HTSUS (USA) | 8535 21 00 00 |
| China customs tariff | 8535 21 00 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
Which voltage classes are the EPR reclosers made for?
The single-phase EPRIS is rated for 15.5 kV, the three-phase EPR for 15.5, 27 and 38 kV. Rated current is 630/800 A or 800 A.
Which protocols do the recloser controllers support?
ETR300-R and EVRC2A-NT work over DNP 3.0, MODBUS and IEC 60870-5-101/104. ETR300-R also supports IEC 61850.
Which standards was the EPR tested to?
Type tests were carried out at KEMA, CESI and KERI to ANSI/IEEE C37.60 and IEC 62271-111. The operating temperature range is −40…+80 °C, degree of protection IP65.