3AP DT / SPS2 — SF6 dead tank circuit breakers 72.5–550 kV

3AP DT and SPS2 are SF6 dead tank circuit breakers for 72.5–550 kV in which the interrupter is housed in a grounded metal tank. Connection to the network is made through bushings with built-in current transformers. The units are installed at substations of grid companies, power plants and industry, especially in seismically active regions.

Rated voltage
72.5–550 kV (3AP1 DT up to 362 kV, 3AP1 DTC up to 245 kV, 3AP2/3 DT up to 550 kV; SPS2/SPS2S 123–550 kV)
Short-circuit breaking current
up to 90 kA (SPS2 123–170 kV: 20–80 kA; SPS2-550: up to 63 kA)
Rated current
1200–5000 A
Break time
3 cycles (2 cycles for 550 kV)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The dead tank layout is traditional for the networks of North and South America. The grounded tank increases seismic withstand, and the bushings are convenient to use for built-in current transformers for metering and protection. All units have the FA spring-operated mechanism and 3AP interrupters shared with the live tank breakers.

The international 3AP DT line covers 72.5–550 kV. The 3AP1 DT is rated up to 362 kV, the compact 3AP1 DTC is made for 145 and 245 kV, and the 3AP2/3 DT up to 550 kV. The breakers come with a common or separate frames, with optional closing resistors and various current transformer options. The maximum breaking current reaches 90 kA, and interruption takes 2 cycles.

For the US market the SPS2/SPS2S series is built at the plant in Richland, Mississippi. Models for 123, 145 and 170 kV have breaking currents of 20, 31.5, 40, 50, 63 and 80 kA at rated currents of 1200–4000 A (up to 5000 A for 80 kA), impulse withstand of 550/650/750 kV and a break time of 3 cycles. No model needs capacitors to limit the rate of rise of recovery voltage. The breakers arrive assembled and tested, are not adjusted on site, and the first inspection is made after 12 years. The SPS2-550 for 550 kV has a rated current of up to 5000 A, a breaking current of up to 63 kA, a break time of 2 cycles and impulse withstand of up to 1800 kV. The mechanical class is M2, the capacitive switching class is C2, and the current transformers are supplied already installed. Versions for 245 and 362 kV are available.

Optionally available are single-pole operation IPO, the PSD controlled switching controller, composite bushings and a high-seismic version to IEEE 693. The breakers are tested to IEC and IEEE/ANSI.

Pure SF6 liquefies at low temperatures, so for cold climates the 3AP1 DT for 126–170 kV with an SF6 and CF4 mixture is offered. With 43 % SF6 it operates down to −50 °C, with 25 % SF6 down to −60 °C, both variants without tank heating. The rated current is 3150 A, the breaking current 40 kA, and the leakage is below 0.1 % per year.

Technical specifications

Rated voltage72.5–550 kV (3AP1 DT up to 362 kV, 3AP1 DTC up to 245 kV, 3AP2/3 DT up to 550 kV; SPS2/SPS2S 123–550 kV)
Short-circuit breaking currentup to 90 kA (SPS2 123–170 kV: 20–80 kA; SPS2-550: up to 63 kA)
Rated current1200–5000 A
Break time3 cycles (2 cycles for 550 kV)
Operating mechanismFA spring-spring
Built-in CTsyes, flexible options
Seismic withstandIEEE 693 (high)
Low temperatures3AP1 DT with SF6/CF4 mixture down to −50/−60 °C without heating
StandardsIEC, IEEE/ANSI

Request a price and lead time

3AP DT / SPS2 — SF6 dead tank circuit breakers 72.5–550 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8535 29 00 00
HS, 6 digits8535 29
CN (EU)8535 29 00
HTSUS (USA)8535 29 00 40
China customs tariff8535 29 00 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Are grading capacitors needed for SPS2 breakers?

No, no SPS2 model for 123–170 kV needs capacitors to limit the rate of rise of recovery voltage. This applies to all breaking currents up to 80 kA.

Which dead tank breaker suits a climate down to −60 °C?

The 3AP1 DT for 126–170 kV with a 25 % SF6 and CF4 mixture is available for such conditions and works without tank heating. With 43 % SF6 the limit is −50 °C, the rated current is 3150 A and the breaking current 40 kA.

What are the parameters of the SPS2-550 dead tank breaker?

The SPS2-550 is rated for 550 kV, a rated current of up to 5000 A and a breaking current of up to 63 kA. The break time is 2 cycles, the impulse withstand up to 1800 kV and the mechanical class M2.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides