International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

3AH47 — vacuum circuit breaker for traction substations and railway electrification up to 27.5 kV (16.7/25/50/60 Hz)

A vacuum circuit breaker for traction substations and sectioning posts of AC catenary systems rated up to 27.5 kV. Breaking current is up to 50 kA, rated current up to 2500 A. It operates at 16.7 Hz, 25 Hz and 50/60 Hz.

Rated voltage
up to 27.5 kV
Breaking current
up to 50 kA
Rated current
up to 2500 A
Frequency
16.7; 25; 50/60 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

3AH47 is built on the proven modular 3AH platform. It combines a repeatedly tested vacuum circuit-breaker set with the flexibility required by the various traction power supply systems around the world.

The breaker supports 16.7 Hz systems used in Germany, Austria, Switzerland and Scandinavia, as well as 25 Hz and 50/60 Hz, and various regional requirements. Rated voltage is up to 27.5 kV, short-circuit breaking current up to 50 kA, rated current up to 2500 A. Endurance is up to 60,000 switching operations with simple maintenance, which matters for catenary feeders with frequent trips and reclosing.

An optional capacitor trip device is provided for fast fault clearing and for keeping the breaker operable if the control supply is lost. The vacuum interrupter is sealed and requires no maintenance of the arc-quenching medium. Catenary feeders suffer frequent short circuits because of line faults, so endurance and fast reclosing are important for the breaker. During selection, the system frequency, voltage, short-circuit current at the installation point, the supply scheme and the railway operator's feeder protection requirements are checked. Detailed data, including single- or two-pole versions, test voltages and dimensions, are not given on the downloaded page and are clarified from the catalog.

Applications include traction substations and sectioning posts of 25 kV 50 Hz AC railways, 2×25 kV systems, and single-phase 15 kV 16.7 Hz traction networks.

Technical specifications

Rated voltageup to 27.5 kV
Breaking currentup to 50 kA
Rated currentup to 2500 A
Frequency16.7; 25; 50/60 Hz
Enduranceup to 60,000 operations with simple maintenance
Optionstripping from a capacitor trip device
Platformmodular 3AH

Request a price and lead time

3AH47 — vacuum circuit breaker for traction substations and railway electrification up to 27.5 kV (16.7/25/50/60 Hz). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which frequencies is the 3AH47 rated for?

16.7 Hz, 25 Hz and 50/60 Hz, so the breaker suits various traction power supply systems.

What are the rated parameters of the breaker?

Voltage up to 27.5 kV, breaking current up to 50 kA, rated current up to 2500 A.

Which traction systems is the breaker used in?

In 25 kV 50 Hz AC railways, 2×25 kV systems and single-phase 15 kV 16.7 Hz networks.