ODFPS 1000 kV — single-phase extra-high-voltage autotransformers (including site-assembled versions)

TBEA ODFPS are single-phase oil-immersed 1000 kV class autotransformers rated 1000 and 1500 MVA for extra-high-voltage substations. They connect the 1000 and 500 kV grids on AC trunk lines. The ODFPS-JT version is delivered in parts and assembled on site.

Type
single-phase oil-immersed autotransformer with off-circuit tap changing, main and regulating-compensating transformers
Rating
1 000 000 kVA (ODFPS-1000000/1000); 1 500 000 kVA (ODFPS-JT-1500000/1000, assembled on site)
Voltages
(1050/√3)/(525/√3)/110 kV
Short-circuit voltage
HV-MV 18 %, HV-LV 62 %, MV-LV 40 %

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

1000 kV class autotransformers work on the extra-high-voltage AC lines that make up China's trunk grids. The company supplied the first 1000 kV transformer in the industry for the Jindongnan–Nanyang–Jingmen pilot line, and its units also operate on the Huainan–Zhebei–Shanghai and Sichuan–Chongqing lines. Through them, large amounts of power are transmitted over long distances with low losses.

The basic ODFPS-1000000/1000 version is rated 1000 MVA. It is a single-phase three-winding unit with off-circuit tap changing, which according to the manufacturer is the largest in the world in voltage and power among transformers of this type. The rated voltages are (1050/√3)/(525/√3 ±4×1.25 %)/110 kV, the frequency is 50 Hz, and the vector group is Ia0i0. The short-circuit voltages are 18 % for the HV-MV pair, 62 % for HV-LV and 40 % for MV-LV. The HV insulation levels are SI1800, LI2250 and AC1100 kV.

The unit consists of a main transformer with OFAF cooling and a regulating and compensating transformer with ONAN cooling. A new compensation scheme limits voltage fluctuations during regulation. No-load losses do not exceed 200 kW and short-circuit losses 1490 kW. The top oil temperature rise is not more than 55 K, that of the hottest spot of the winding 78 K, and the noise level is up to 75 dB(A). Stray fields of large currents are suppressed, so there are no local overheating spots and short-circuit withstand is high.

The ODFPS-JT-1500000/1000 version rated 1500 MVA is transported disassembled and assembled on site, so dimensions and weight during transport are no longer a limitation. The core has a frame design, the active part and leads are convenient to install, and drying is done by a mobile unit on site. Cooling is ODAF, no-load losses are 280 kW and short-circuit losses 2270 kW, the sound pressure level is not more than 78 dB(A), and the regulation range is ±41.25 % in the medium-voltage circuit. Both versions have an explosion-proof design with high mechanical strength. They are installed at 1000 kV substations of trunk grids and interregional links.

Technical specifications

Typesingle-phase oil-immersed autotransformer with off-circuit tap changing, main and regulating-compensating transformers
Rating1 000 000 kVA (ODFPS-1000000/1000); 1 500 000 kVA (ODFPS-JT-1500000/1000, assembled on site)
Voltages(1050/√3)/(525/√3)/110 kV
Short-circuit voltageHV-MV 18 %, HV-LV 62 %, MV-LV 40 %
HV insulationSI1800 / LI2250 / AC1100 kV
CoolingOFAF (main), ONAN (regulating); ODAF (JT version)
No-load / short-circuit losses≤200 / ≤1490 kW (1000 MVA); 280 / 2270 kW (1500 MVA)
Noise≤75 dB(A) / ≤78 dB(A)
Frequency50 Hz

Replacement for

no direct serial analogue; the closest is АОДЦТН-667000/1150/500 (a one-off unit for 1150 kV lines)

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

ODFPS 1000 kV — single-phase extra-high-voltage autotransformers (including site-assembled versions). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8504 23 00 00
HS, 6 digits8504 23
CN (EU)8504 23 00
HTSUS (USA)8504 23 00 80
China customs tariff8504 23 10 00
8504 23 20 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What voltages and ratings does the ODFPS autotransformer have?

Rated voltages (1050/√3)/(525/√3 ±4×1.25 %)/110 kV. Rating 1000 MVA in the basic version and 1500 MVA in the ODFPS-JT version.

What cooling is used in the ODFPS?

The main transformer has OFAF cooling and the regulating and compensating transformer has ONAN. The ODFPS-JT-1500000/1000 version is cooled by the ODAF scheme.

How is the 1500 MVA unit delivered if roads do not allow large dimensions?

The ODFPS-JT-1500000/1000 is delivered disassembled and assembled on site, and drying is done by a mobile unit. Its no-load losses are 280 kW and short-circuit losses 2270 kW.