International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

FastWorks — preconfigured 33 kV and 132 kV power transformers with shorter lead time

Preconfigured 33 kV and 132 kV power transformers in ready-made configurations without additional engineering. Manufacturing time is up to 24 weeks for 33 kV and up to 52 weeks for 132 kV. Ratings from 7.5 to 90 MVA, for network company substations, BESS, renewables and data centres.

132 kV versions
60/90 MVA, 132/33 kV, YNd11/YNd1, ONAN/OFAF-CMR, built-in vacuum OLTC +10/−20 % (19 positions)
33 kV versions
7.5/10/15 MVA and 12/16/24 MVA, 33/11.5 kV, Dyn11, ONAN/OFAF-CMR/OFAF-CER, externally mounted vacuum OLTC ±10 % (17 positions)
132 kV insulation levels
HV 650/230 kV, neutral 95/38 kV; LV 170/70 kV
Weight
106 t (132 kV); 22.7 t (33 kV, 7.5–15 MVA)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

FastWorks is a range of preconfigured power transformers for UK grid infrastructure, created for projects where speed of deployment is decisive. Unlike custom-designed transformers, they are supplied in ready-made 33 kV and 132 kV configurations without additional engineering. This shortens the manufacturing time to 24 weeks for 33 kV and 52 weeks for 132 kV. The transformers are manufactured in the United Kingdom and comply with IEC 60076, Tier 2 requirements and the UK standards ENA TS 35-2 and 35-3. Warranty 2.5 years, design service life over 40 years.

The 132 kV version: 60/90 MVA, 132/33 kV, vector groups YNd11 or YNd1, ONAN/OFAF-CMR cooling. The built-in vacuum OLTC has a range of +10/−20 % in steps of 1.67 % (18 steps, 19 positions). Insulation levels are HV 650 kV impulse and 230 kV with graded insulation down to 95/38 kV at the neutral, LV 170/70 kV. Noise is specified to ENA TS 35-3, HV bushings are outdoor, and the LV side has a cable box. Weight 106 t, dimensions 7800×5600×6800 mm.

The 33 kV versions are rated 7.5/10/15 MVA and 12/16/24 MVA, voltage 33/11.5 kV, vector group Dyn11. Cooling is ONAN, OFAF-CMR or OFAF-CER. The externally mounted vacuum OLTC regulates voltage within ±10 % in steps of 1.25 % (17 positions). Insulation is HV 170/70 kV, LV 75/28 kV. For the first version, weight is 22.7 t and dimensions are 4350×3450×3750 mm.

The equipment includes mounted radiators, fans, a gas relay, a pressure relay, winding and oil temperature indicators, a magnetic oil level indicator, built-in current transformers, a terminal cabinet and a remote OLTC control panel. An example is three FastWorks 33/11.5 kV 20/25/40 MVA transformers in Coventry, installed 30 weeks after the order. Applications include DNO substations, BESS and renewables, and connection of data centres and industrial sites at 33 and 132 kV.

Transformers are fully assembled and tested at the factory in Loughborough (United Kingdom). The test facility, which complies with IEC (BS EN) and ENA, performs routine and type tests up to 170 kV, including impulse, temperature rise, SFRA, and measurement of partial discharge, losses and noise level. Technical support is available around the clock, 365 days a year.

Technical specifications

132 kV versions60/90 MVA, 132/33 kV, YNd11/YNd1, ONAN/OFAF-CMR, built-in vacuum OLTC +10/−20 % (19 positions)
33 kV versions7.5/10/15 MVA and 12/16/24 MVA, 33/11.5 kV, Dyn11, ONAN/OFAF-CMR/OFAF-CER, externally mounted vacuum OLTC ±10 % (17 positions)
132 kV insulation levelsHV 650/230 kV, neutral 95/38 kV; LV 170/70 kV
Weight106 t (132 kV); 22.7 t (33 kV, 7.5–15 MVA)
Lead time24 weeks (33 kV), 52 weeks (132 kV)
Service life>40 years
Warranty2.5 years
ComplianceIEC 60076, Tier 2, ENA TS 35-2/35-3

Replacement for

ТМН-6300/35, ТД-10000/35, ТДН-16000/110, ТРДН-40000/110, ТРДЦН-63000/110, ТРДЦН-80000/110; accelerated delivery — none

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

FastWorks — preconfigured 33 kV and 132 kV power transformers with shorter lead time. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What are the manufacturing times for FastWorks transformers?

Up to 24 weeks for 33 kV versions and up to 52 weeks for 132 kV. The reduction comes from ready-made configurations without additional engineering.

What ratings and voltages are available in FastWorks versions?

The 132 kV version is rated 60/90 MVA at 132/33 kV. The 33 kV versions are rated 7.5/10/15 and 12/16/24 MVA at 33/11.5 kV.

What insulation levels and voltage regulation does the 132 kV version have?

HV 650 kV impulse and 230 kV, neutral 95/38 kV, LV 170/70 kV. The OLTC is a built-in vacuum type with a range of +10/−20 % in steps of 1.67 %.

Similar equipment from other manufacturers