International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

e4 Ultimate Low Loss Amorphous — amorphous-core distribution transformers up to 3 MVA, 11/0.415 kV

Amorphous-core distribution transformers rated 315–3000 kVA, 11 000/415 V, vector group Dyn11. Total losses are 27 % lower than the Ecodesign Tier 2 requirements. They are used at universities, hospitals, retail chains, industrial sites and data centres.

Rating
315–3000 kVA
Voltage
11 000/415 V (others on request)
Core
amorphous alloy (AMTx)
Windings
aluminium

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

e4 Ultimate Low Loss Amorphous is the third generation of amorphous distribution transformers and, according to the manufacturer, the most energy-efficient distribution transformer in Europe. Work on the range began in 2008 (e2 was the first amorphous transformer in the UK), followed by e3 (2018) and e4 (2024). More than 2300 amorphous transformers have been installed in the UK; in 16 years of operation no core failure has been recorded.

The core (designated AMTx) is wound from amorphous alloy ribbon, that is, metal rapidly cooled from the melt without forming a crystal lattice. The disordered structure and high resistivity reduce magnetisation losses and eddy currents. Together with low current density conductors, this gives minimal total losses, 27 % lower than the Ecodesign Tier 2 (2021) requirements.

The rating range comprises 315, 500, 800, 1000, 1250, 1500, 1600, 2000, 2500 and 3000 kVA, 11 000/415 V, Dyn11, aluminium windings. Transformers up to 1250 kVA are built without radiators. The secondary voltage is lowered to 415 V (instead of 433 V), and +7.5 % is added to the standard five taps, so the voltage at the site can be reduced without additional equipment. No-load/load losses are 215/1940 W for 315 kVA, 675/8630 W for 1600 kVA and 1150/19 000 W for 3000 kVA, all values at 75 °C.

Cooling is ONAN on mineral oil or KNAN on synthetic or natural ester, with free breathing or a hermetically sealed tank. Manufacture is to IEC 60076 or the customer's specification. The off-circuit tap changer has six positions and can be sealed. Painting is to BS 381C (shade 632) and ISO 12944 not lower than C4H. A general arrangement drawing with RMU and LV cabinets is available. Warranty 24 months.

On economics, replacing a 1990s transformer saves up to £380 thousand over its service life, and the payback period of a 1000 kVA unit compared with a 1970s unit is about 2 years at 70 % load. Applications: universities, hospitals, retail chains, industry, data centres, charging hubs.

Technical specifications

Rating315–3000 kVA
Voltage11 000/415 V (others on request)
Coreamorphous alloy (AMTx)
Windingsaluminium
HV taps+7.5; +5; +2.5; 0; −2.5; −5 % (off-circuit)
CoolingONAN (mineral oil) or KNAN (synthetic/natural ester)
Vector groupDyn11
No-load / load losses at 75 °C215/1940 W (315 kVA); 675/8630 W (1600 kVA); 1150/19 000 W (3000 kVA)
Efficiencytotal losses 27 % below Tier 2
Breathingfree or hermetically sealed
StandardsIEC 60076

Replacement for

ТМГ-…/10 (energy-efficient ТМГ11, ТМГ12); no serial analogue with an amorphous core

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

e4 Ultimate Low Loss Amorphous — amorphous-core distribution transformers up to 3 MVA, 11/0.415 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What ratings and voltage does the range cover?

315, 500, 800, 1000, 1250, 1500, 1600, 2000, 2500 and 3000 kVA at 11 000/415 V. Vector group Dyn11, aluminium windings.

What losses do these transformers have?

No-load/load losses are 215/1940 W for 315 kVA, 675/8630 W for 1600 kVA and 1150/19 000 W for 3000 kVA. Total losses are 27 % below Ecodesign Tier 2.

Why is the secondary voltage lowered to 415 V?

415 V is adopted instead of 433 V, and +7.5 % is added to the standard five taps. This lowers the voltage at the site without additional equipment.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00