International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ERIS2, combined protective relay for sealed transformers with 4–20 mA outputs

The eRIS2 is the digital version of the integrated safety device for sealed transformers, with 4–20 mA analog outputs for oil temperature and tank pressure. The unit combines a pressure relay, thermostats, an oil level indicator and a gas relay in one enclosure on the transformer cover.

Standard
IEC 60076-22-1
Analog outputs
temperature 4–20 mA (0–160 °C); pressure 4–20 mA (0–500 mbar; −1000…+1000 mbar to order)
Analog line length
up to 30 m
Accuracy
thermostats ±4 °C; pressure relay ±10; thermometer ±3 °C

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The basic RIS2 gives only discrete alarm and trip signals. According to the manufacturer, the eRIS2 became the first device of this class with analog outputs for continuous remote monitoring of temperature and pressure. The functions of four devices, namely the pressure relay, thermostats, oil level indicator and gas relay, remain in one compact enclosure on the transformer cover.

The current values of oil temperature and tank pressure are transmitted continuously. This shows pressure fluctuations in the corrugated walls and radiators of a sealed transformer, and a developing fault can be noticed before the protection operates. The 4–20 mA temperature output is proportional to the range 0–160 °C. The 4–20 mA pressure output corresponds to 0–500 mbar, or −1000…+1000 mbar to order. The analog line length is up to 30 m. In a sealed tank the pressure changes together with the oil temperature, and the overpressure relay is usually set within 0.3–0.5 bar. Vacuum inside the tank is also dangerous, because it reduces the breakdown voltage of the oil, so the pressure trend is useful in both directions.

The level indicator has a 270° viewing angle, and the pressure setpoints are adjustable. The accuracy is ±4 °C for the thermostats, ±10 of scale for the overpressure relay and ±3 °C for the thermometers. The maximum operating pressure is 500 mbar. The enclosure has a degree of protection IP66, IP67 to order, impact resistance IK07, and resistance to salt fog of 1000 h and to UV of 500 h. The ambient temperature is from −40 to +60 °C, and the oil temperature up to 120 °C.

The cable gland is M25×1.5, and the terminals accept conductors up to 2.5 mm². The level and gas contacts are rated 24–230 V DC and 2 A, and the pressure relay 24–230 V AC and 2 A. The unit complies with IEC 60076-22-1, belongs to the eDevices family and can work in the MeDICA monitoring ecosystem. The eRIS2 is fitted to sealed distribution and small power transformers, smart transformers, solar plants, offshore and tropical sites, installations with harsh conditions, new substations and upgrades.

Technical specifications

StandardIEC 60076-22-1
Analog outputstemperature 4–20 mA (0–160 °C); pressure 4–20 mA (0–500 mbar; −1000…+1000 mbar to order)
Analog line lengthup to 30 m
Accuracythermostats ±4 °C; pressure relay ±10; thermometer ±3 °C
Max. pressure500 mbar
Degree of protectionIP66 (IP67 to order); IK07
Salt fog / UV1000 h / 500 h
Ambient temperature−40…+60 °C

Request a price and lead time

ERIS2, combined protective relay for sealed transformers with 4–20 mA outputs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)9026 20 20 00
HS, 6 digits9026 20
CN (EU)9026 20 20
HTSUS (USA)9026 20 40 00
China customs tariff9026 20 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which analog signals does the eRIS2 provide?

Oil temperature 4–20 mA over the range 0–160 °C and pressure 4–20 mA over the range 0–500 mbar, or −1000…+1000 mbar to order. The analog line is up to 30 m.

What is the measurement accuracy of the eRIS2?

Thermostats ±4 °C, overpressure relay ±10 of scale, thermometer ±3 °C.

What conditions does the eRIS2 work in?

At an ambient temperature from −40 to +60 °C and an oil temperature up to 120 °C. The degree of protection is IP66, or IP67 to order, and the impact resistance is IK07.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides