COMTRAXX® COM465DP condition monitor with PROFIBUS DP and Ethernet gateway, AC/DC 24…240 V
The COMTRAXX® COM465DP is a condition monitor with a built-in gateway to PROFIBUS DP and Ethernet-TCP/IP networks. It speaks Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT and OPC UA. Supply AC/DC 24…240 V.
- Type
- Condition monitor with integrated gateway
- Networks
- PROFIBUS DP, Ethernet-TCP/IP
- Protocols
- PROFIBUS DP, Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM, OPC UA
- Interfaces
- RS-485, Ethernet, USB
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A condition monitor and a protocol gateway in one housing: the COMTRAXX® COM465DP connects the manufacturer's monitoring devices to PROFIBUS DP and Ethernet-TCP/IP networks. Alarms, measured values and device states are converted into protocols such as Modbus TCP, SNMP and HTTP. That couples them to standard networks and makes them visible in a web browser.
On the device side it works with the BMS bus and the BCOM interface; the unit itself has RS-485, Ethernet and USB. Supported protocols are PROFIBUS DP, Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM and OPC UA. The device's own parameters are set in a web interface, and remote access runs over Ethernet. A history memory and configurable data loggers are included, and time synchronisation covers the assigned devices.
Function modules A to F extend the base unit. Module A adds individual text messages, device failure monitoring and e-mail. Module B provides data over Modbus TCP, Modbus RTU, SNMP and PROFINET. Module C sets parameters on all integrated devices and keeps device backups. Module D is a visualisation application, module E adds virtual devices, and module F integrates third-party devices. External applications such as PLCs can read the data without extra PC software.
The supply is AC/DC 24…240 V with a consumption of no more than 6,5 VA / 4 W. Rated voltage is AC 250 V, rated impulse withstand voltage 4 kV, overvoltage category III and pollution degree 3. The housing measures 62,9 x 107,5 x 48,5 mm.
Mounting is on a DIN rail or with screws (3 x M4), and the supply needs a 6 A fuse. The variant for PROFIBUS DP and Ethernet is COM465DP-230V.
Technical specifications
| Type | Condition monitor with integrated gateway |
|---|---|
| Networks | PROFIBUS DP, Ethernet-TCP/IP |
| Protocols | PROFIBUS DP, Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM, OPC UA |
| Interfaces | RS-485, Ethernet, USB |
| Supply voltage Us | AC/DC 24…240 V |
| Frequency | DC, 50…60 Hz |
| Power consumption | ≤ 6,5 VA / ≤ 4 W |
| Rated voltage | AC 250 V |
| Rated impulse withstand voltage | 4 kV |
| Overvoltage category | III |
| Pollution degree | 3 |
| Dimensions | 62,9 x 107,5 x 48,5 mm |
| Mounting | DIN rail, screws (3 x M4) |
Part numbers
Show all part numbers (2)
B95061060, modules B75061011…B75061016
How it compares with similar models
| Parameter | COMTRAXX® COM465DP condition monitor with PROFIBUS DP and Ethernet gateway, AC/DC 24…240 V | COMTRAXX® COM463BC gateway between BCOM and an external BMS, AC/DC 24…240 V | COMTRAXX® COM465IP condition monitor with Ethernet gateway, AC/DC 24…240 V | COMTRAXX® EDGE500IP condition monitor with gateway, 2 x Ethernet, RS-485, DC 24 V |
|---|---|---|---|---|
| Type | Condition monitor with integrated gateway | — | Condition monitor with integrated gateway | Condition monitor with gateway functions |
| Protocols | PROFIBUS DP, Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM, OPC UA | — | Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM | Modbus TCP, Modbus RTU, SNMP, MQTT, PROFINET, OPC UA, HTTP, HTTPS, DHCP, NTP, SMTP, BCOM |
| Interfaces | RS-485, Ethernet, USB | RS-485, Ethernet | RS-485, Ethernet | 2 x Ethernet, RS-485, USB |
| Rated voltage | AC 250 V | AC 250 V | — | AC 50 V |
Request a price and lead time
COMTRAXX® COM465DP condition monitor with PROFIBUS DP and Ethernet gateway, AC/DC 24…240 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which protocols does the COM465DP support?
PROFIBUS DP, Modbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOM and OPC UA. Data over Modbus TCP, Modbus RTU, SNMP and PROFINET is enabled by module B.
What are function modules A to F for?
They extend the base unit. Module C, for example, sets parameters on integrated devices and keeps their backups, and module F integrates third-party devices.
How does the COM465DP differ from the COM465IP?
The DP version connects to PROFIBUS DP and Ethernet, while the COM465IP works with Ethernet only.