International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

COMTRAXX® COM463BC gateway between BCOM and an external BMS, AC/DC 24…240 V

The COMTRAXX® COM463BC exchanges data between the BCOM interface and external BMS systems. It has RS-485 and Ethernet ports and is configured through a web interface. Supply AC/DC 24…240 V, DIN rail or screw mounting.

Function
Gateway between the BCOM interface and an external BMS
Interfaces
RS-485, Ethernet
Supply voltage
AC/DC 24…240 V
Frequency
50…60 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Where an installation already runs an external BMS, the COMTRAXX® COM463BC links it with BCOM. The gateway passes information between the two interfaces, and what is transferred from one system to the other is set in the configuration. Several external BMS systems can then appear together with BCOM systems in one overview.

The external BMS bus goes to the RS-485 port and the BCOM network to the Ethernet port. All settings are made in a built-in web interface, so measured values and alarms can be viewed and the exchange configured from a browser, locally or remotely. Remote diagnosis and remote maintenance need no extra software on the PC.

Capacity is up to 99 x 150 external BMS devices and 255 BCOM devices, plus 100 virtual devices with 16 channels each. Different users can be notified selectively by e-mail about alarms and system errors.

The supply is AC/DC 24…240 V at 50…60 Hz with a consumption of no more than 6,5 VA / 4 W. Rated voltage is AC 250 V, rated impulse voltage 4 kV, pollution degree 3, and the operating temperature range is –25…+55 °C. The housing measures 107,5 x 93 x 62,9 mm and weighs up to 240 g.

The unit clips onto a DIN rail or is fixed with screws (3 x M4). The supply line should carry a 6 A fuse. Design references are IEC 60664-1, IEC 60529, IEC 60715 and EN 61326-1, and the device complies with the RoHS directives.

Technical specifications

FunctionGateway between the BCOM interface and an external BMS
InterfacesRS-485, Ethernet
Supply voltageAC/DC 24…240 V
Frequency50…60 Hz
Power consumption≤ 6,5 VA / ≤ 4 W
Rated voltageAC 250 V
Rated impulse voltage4 kV
Pollution degree3
Operating temperature–25…+55 °C
Dimensions107,5 x 93 x 62,9 mm
Weight≤ 240 g
MountingDIN rail, screws (3 x M4)

Part numbers

Show all part numbers (1)

B95061051

How it compares with similar models

ParameterCOMTRAXX® COM463BC gateway between BCOM and an external BMS, AC/DC 24…240 VCOMTRAXX® COM465DP condition monitor with PROFIBUS DP and Ethernet gateway, AC/DC 24…240 VCOMTRAXX® MK2430 alarm indicator and test combination with LC display, AC/DC 24 VCOMTRAXX® COM465IP condition monitor with Ethernet gateway, AC/DC 24…240 V
InterfacesRS-485, EthernetRS-485, Ethernet, USBRS-485, USB (V2.0/V1.1)RS-485, Ethernet
Power consumption≤ 6,5 VA / ≤ 4 W≤ 6,5 VA / ≤ 4 W≤ 3 VA≤ 6,5 VA / ≤ 4 W
Dimensions107,5 x 93 x 62,9 mm62,9 x 107,5 x 48,5 mm171 x 100.5 x 59 mm—

Request a price and lead time

COMTRAXX® COM463BC gateway between BCOM and an external BMS, AC/DC 24…240 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which interfaces does the COM463BC have?

RS-485 for the external BMS bus and Ethernet for BCOM. Configuration is done in the built-in web interface.

How many devices can the gateway handle?

Up to 99 x 150 external BMS devices and 255 BCOM devices, plus 100 virtual devices with 16 channels each.

How is the supply protected?

With a 6 A fuse. The supply is AC/DC 24…240 V at 50…60 Hz.